beautypg.com

Troubleshooting – Fire Fighting Enterprises FIRERAY 5000 User Manual

Page 15

background image

15

E-00 AIM not

recognised

• Refer to manufacturer

for technical assistance

E-08

Compensation

Level Not Zero

during ‘SET’

• Re-align Detector using Auto-

Align

E-01

Detector

Communications

Error

• Check wiring between

System Controller and

Detector (Voltage to

Detector should be

11—13V)

E-09

Signal Strength

Out of Range

when ‘SET’

selected

• Ensure Reflector uncovered

when ‘SET’ selected

• Ensure clear line of sight from

Detector to Reflector for a radius

of 0.5m

• Ensure correct distance has

been selected

• Ensure correct Reflectors have

been used

• Realign Detector

E-02

Detector is

connected but not

‘Found’

• Follow ‘Find’ process

and align if necessary

E-10

Reflector Not

Found during

Auto-Align

• Ensure clear line of sight from

Detector to Reflector for a radius

of 0.5m

• Ensure correct distance has

been selected

• Ensure correct Reflectors have

been used

• Realign Detector

E-03 Compensation

limit reached

• Clean and realign

system

E-11 Auto-Align

Failed

• Ensure clear line of sight from

Detector to Reflector for a radius

of 0.5m

• Ensure correct distance has

been selected

• Ensure correct Reflectors have

been used

• Realign Detector

E-04 Detector missed

too many readings

• Check voltage to

Controller.

• Check voltage to

Detector is >11V

E-12

Cannot Zero

During ‘S-00’ in

‘Set’
Signal did not

decrease when

‘S-00’ selected

• Ensure Reflector was

completely covered with a non-

reflective material

• Re-align Detector using Auto-

Align

E-05 Detector is not

aligned

• Follow alignment

procedure

E-13

No Signal

During ‘S-01’ in

‘Set’
Signal did not

increase when

‘S-01’ selected

• Ensure Reflector was uncovered

when ‘S-01’ was selected

E-06 Rapid Obscuration

Fault

• Ensure clear line of

sight from Detector to

Reflector

E-14

‘Centre’ Stage

of Alignment

Failed
Detector has

aligned on

something other

than the

Reflector

• Ensure clear line of sight from

Detector to Reflector for a radius

of 0.5m

E-07 Signal Too High

Fault

• Ensure clear line of

sight from Detector to

Reflector

• Ensure there is no

strong light on Detector

E-21 Power too low

fault

• Check power supply to

Controller

20. Troubleshooting