This setting is the threshold at which the Detector will detect a fire

Default factory setting=35%
(Set for each Detector)

16. Fire Threshold

Complies with EN54-12 for sensitivity levels between 25% and 35% with a maximum delay to

fire of 20 seconds

UL268 Fire Threshold Ranges:

Distance between

Detector and Reflector

Fire Threshold

Range

8—10m (26.2—32.8ft)

10—18%

10—15m (32.8—49.2ft)

15—25%

15—22m (49.2—72.2ft)

15—35%

22—40m (72.2—131.2ft)

25—50%

40—60m (131.2—196.8ft)

35—50%

60—100m (196.8—328.1ft)

50%

12

Sensitivity can be adjusted in 1% steps by pressing up or down keys

Press

to accept setting

EN Approved Sensitivity Ranges: