beautypg.com

Teledyne 4020 - Hydrocarbon analyzer User Manual

Page 37

background image

Total Hydrocarbon Analyzer

Installation

Teledyne

Analytical

Instruments

21

(Reset by pressing the STANDBY button to remove
power. Then press STANDBY again and any other
button except SYSTEM to resume

Further detail can be found in Chapter 4, Section 4.5.15.

Table 3-4: Alarm Relay Contact Pins

Pin Contact

45

Threshold Alarm 1, normally closed contact

28

Threshold Alarm 1, moving contact

46

Threshold Alarm 1, normally open contact

42

Threshold Alarm 2, normally closed contact

44

Threshold Alarm 2, moving contact

43

Threshold Alarm 2, normally open contact

36

System Alarm, normally closed contact

20

System Alarm, moving contact

37

System Alarm, normally open contact

3.3.3.6

D

IGITAL

R

EMOTE

C

AL

I

NPUTS

The digital remote calibration input accepts 0 V (off) or 24 VDC

(on) for remote control of calibration. (See Remote Calibration
Protocol
below.) See Table 3-5 for pin connections.

The remote cal inputs are shared by the digital range selection mode.

When the user selects the digital range selection mode, the input is used
by the analyzer for range selection. See Section 4.6.13.3 Digital Mode.

Zero:

Floating input. A 5–24 V input across the + and –
pins puts the analyzer into the Zero mode. Either side
may be grounded at the source of the signal. A 0–1
volt across the terminals allows Zero mode to
terminate when done. A synchronous signal must
open and close the external zero valve appropriately.

Span:

Floating input. A 5–24 V input across the + and –
pins puts the analyzer into the Span mode. Either
side may be grounded at the source of the signal. A