beautypg.com

Maintenance, Procedure for cleaning the air inlet filter, Relief valve testing – Fulton Reliance (RLN) High Efficiency Cooper Fin Boiler User Manual

Page 45: Annual maintenance and inspection schedule

background image

Questions? Call (315) 298-5121, or visit us online at www.fulton.com

SECTION 4

RLN-IOM-2012-1205

MAINTENANCE

4-3

!

WARNING

All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct,
and strict adherence to applicable
jurisdictional/professional codes and
regulations.

Never use open fl ame or other sources
of ignition to check for gas leaks.

Crystalline silica may be present
in components of this equipment.
Exposure to crystalline silica may
pose signifi cant health hazards,
including but not limited to eye and
respiratory system damage. Per
the Centers for Disease Control and
Prevention (CDC) and Occupational
Safety and Health Administration
(OSHA), appropriate personal
protective equipment must be worn
to minimize exposure to hazardous
substances. Refer to most current
guidelines off ered by the CDC and
OSHA for more information, including
personal protective equipment
recommendations.

4

CAUTION

Use caution when using any cleaning
solutions. Refer to local regulations for
proper cleaning solution disposal.

Do not allow oil leaks, dust, or dirt to
accumulate around the boiler.

Hazard analysis should be performed
by end user to ensure safety of
employees/personnel.

Any damage to the burner or any
other aspect of the boiler because of
an air fi lter that was not cleaned and
maintained regularly will void the
warranty on the Reliance boiler.

5. Test the water fl ow switch by trying to restart boiler with system pump off .

The boiler should not operate.

6. If an air inlet fi lter is included with the boiler, inspect and clean fi lter of any

dust or lint. See Procedure for Cleaning the Air Inlet Filter.

7. Verify the water loop style traps in the exhaust venting system are fl ooded.

Procedure for Cleaning the Air Inlet Filter

The air fi lter is an optional part and does not come with every boiler.

Proceed as follows:

1. Remove the fi lter. The fi lter sits in a custom slot on the air inlet connection

to the boiler.

2. Remove all debris and dirt from the fi lter using a non-corrosive soap and

water.

3. Return the fi lter to its original position in the slot.

Relief Valve Testing

The relief valve should be tested as per manufacturer instructions or every two
months by lifting the lever for 5 seconds and allowing the valve to snap shut.
Please see the manufacturer’s recommendations on the relief valve tag.

Annual Maintenance and Inspection Schedule

Annual maintenance and inspection must be performed prior to each heating
season, and includes the following tasks which must be done by a factory trained
technician.

Observe the general operation of the unit to verify the following:

1. Stack temperature readings are in line with factory test fi re and regular

maintenance reports.

2. Boiler is lighting off reliably and quietly.

3. There are no unusual sounds coming from the burner or blower assembly.

4. It is considered good practice to remove and inspect the burner and

ignition assembly on an annual basis. Follow Procedure for Removing/
Cleaning Burner
in this manual if there is evidence of foreign matter built
up on the burner or ignition assembly. See Figure 22.

5. It is considered good practice to inspect the copper fi nned tubes in the

heat exchanger on an annual basis. This can be done from the inside of
the heat exchanger while the burner is removed, or by removing the front
outer jacket panel.

To remove the outer jacket panel, open the front lower door of the outer