Leak Testing

Use a soap solution or equivalent for leak testing. Leak testing solution must be non-corrosive, and be
rinsed off immediately after the leak test. Never test for leak with an open flame. Failure to comply could
result in personal injury, property damage or death.

Always leak test final gas assembly for gas leaks according to the procedures outlined in NFPA 54 and
all local codes and/or Standards.

For leak testing on pressures below 1/2 PSI

Before leak testing, close the field installed manual shut off valve shown on Figure 3.24 on the supply
line to isolate the gas valve from the pressure.

NOTE: All factory installed gas connections have passed

an approved leak test.

For leak testing on pressures above 1/2 PSI

When leak testing with pressures above 1/2 PSI (14 inches W.C.), the unit must be isolated from the
supply pipe. Close the field installed manual shut off valve, disconnect the supply line to the unit, and
temporarily cap the supply line for testing purposes.

WARNING

!

Gas pressures to the appliance controls must never exceed 14 inches W.C. (1/2 PSI).
Supply pressures greater than 14” W.C. can damage the controls, resulting in personal
injury, property damage, or death.

WARNING

!

Testing for gas leaks with an open flame or other sources of ignition may lead
to a fire or explosion and cause serious injury or death. Test in accordance
with NFPA or local codes.

3.0

Installation

Leak Testing

Chart 3.9

Maximum capacity for Schedule 40 Metallic pipe, in CFH

Pipe

Length

1/2”

3/4”

1”

1-1/4”

1-1/2”

2”

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

Nat

Prop

10 feet

132

86

278

182

520

340

1050

686

1600

1046

3050

1993

20 feet

92

60

190

124

350

229

730

477

1100

719

2100

1373

30 feet

73

48

152

99

285

186

590

386

890

582

1650

1078

40 feet

63

41

130

85

245

160

500

327

760

497

1450

948

50 feet

56

37

115

75

215

141

440

288

670

438

1270

830

60 feet

50

33

105

69

195

127

400

261

610

399

1150

752

70 feet

46

30

96

63

180

118

370

242

560

366

1050

686

80 feet

43

28

90

59

170

111

350

229

530

346

990

647

90 feet

40

26

84

55

160

105

320

209

490

320

930

608

100 feet

38

25

79

52

150

98

305

199

460

301

870

569

125 feet

34

22

72

47

130

85

275

180

410

268

780

510

150 feet

31

20

64

42

120

78

250

163

380

248

710

464

175 feet

28

18

59

39

110

72

225

147

350

229

650

425

200 feet

26

17

55

36

100

65

210

137

320

209

610

399