Detroit Radiant Products Company LS3 Series User Manual
Page 11
11
LS3
Series
* Optional protective guard (P/N: PG) is required when mounting below 8-ft.
Factory recommended mounting heights are listed as a guideline. If infrared heaters are mounted too low
or too high, they may result in discomfort or lack of heat. Detroit Radiant Products Company generally
recommends observing the recommended mounting heights to optimize comfort conditions. However,
certain applications such as spot heating, freeze protection, outdoor patio heating or very high ceilings
may result in the heaters being mounted outside of the factory recommended mounting heights.
Figure 3.1
•
Mounting Height Dimensions • see Chart 3.1 for dimensions
Chart 3.1 •
Recommended Mounting Heights and Coverages
NOTE: This chart is provided as a guideline. Actual conditions may dictate variation from this data.
3.0
Installation • Recommended Mounting Heights
Note: Dimensions A, B & C are based upon heaters hung at the factory recommended mounting height.
Dim. C
Dim. A
Dim. B
Dim. C
Dim. A
M
o
d
el
M
ax
im
u
m I
n
pu
t
(BT
U
/h
)
R
ecom
m
end
ed
M
oun
ting
H
eig
h
t
(f
t.
)*
Co
ver
ag
e A
rea
S
tr
ai
g
h
t C
on
fi
g
.
(L
xW)
Co
ver
ag
e A
rea
U
-T
ub
e C
on
fi
g
.
(L
xW)
D
ist
anc
e B
et
w
ee
n
H
ea
te
rs (
ft
.)
D
im
en
sio
n
A
D
ist
anc
e B
et
w
ee
n
H
ea
te
r R
ow
s (
ft
.)
D
im
en
sio
n
B
M
ax
im
um
D
is
ta
n
ce
B
et
w
ee
n H
ea
te
rs
an
d W
al
l (
ft
.)
D
im
en
sio
n
C
10 ft.
25,000
8’ - 11’
20’ x 12’
N/A
10’ - 20’
20’ - 40’
16’
30,000
8’ - 11’
20’ x 12’
N/A
10’ - 20’
20’ - 40’
16’
15 ft.
25,000
8’ - 13’
20’ x 12’
N/A
10’ - 20’
20’ - 40’
16’
30,000
8’ - 13’
20’ x 12’
N/A
10’ - 20’
20’ - 40’
16’
40,000
8’ - 13’
20’ x 12’
N/A
10’ - 20’
20’ - 40’
16’
50,000
10’ - 15’
22’ x 15’
N/A
20’ - 30’
30’ - 50’
18’
20 ft.
40,000
8’ - 13’
20’ x 13’
12’ x 12’
10’ - 20’
20’ - 40’
16’
50,000
9’ - 15’
22’ x 15’
12’ x 12’
20’ - 30’
30’ - 50’
18’
30 ft.
50,000
9’ - 14’
32’ x 15’
15’ x 15’
20’ - 30’
30’ - 50’
18’