Maintenance

Troubleshooting Guide

*

NOTICE

Bypassing any switch is intended for testing purposes only. Do not leave switch bypassed
during normal operation or the heater’s built-in safety mechanisms will be compromised.

Key

Start

Question

Process

Question

Corrective

Action

Is there 120V on the

common side of the

fan relay?

Yes

No

Find source of electrical problem

between the outlet and low fire relay.

Is there 120V on the

N.O. side of the fan

relay?

Yes

The blower assembly

is faulty and must be

replaced.

No

The fan relay is faulty and

must be replaced.

Is there 24V across

the circuit board with

terminal to ground?

No

Repair faulty wiring.

Check both high temperature spark

wires and both electrodes. If good,

replace circuit board.

Yes

Check for loose wiring or restrictions

in the hose connections to pressure

switches. Are they OK?

No

Replace wiring or hose connections.

Replace the pressure switch after verifying:
• Heater, fan blowers ,squirrel cage, intake

and exhaust are clean and free from dirt and

obstructions.

• The 4” air intake pipe does not exceed 30 ft. and/or

2 elbows.

• There is not a negative pressure experienced at

the area of air intake (e.g.; high winds, attic space,

tightly sealed building). May vary for agricultural

buildings (consult factory).

Yes