3.0

Installation

Venting

Common Venting

Figure 3.13

Common Rooftop Venting - Side View

Common Venting

• When joining two heaters to a common vent, a staggered arrangement or a dual exhaust assembly

(P/N: YSM) must be used so by-products of one heater do not flow into the adjoining vent of the

other heater.

• 6 in. diameter double-wall Type B-vent and 6 in. vent cap must be used.

• Common vented heaters

must be controlled with the same thermostat. Do not operate individually.

Figure 3.14

Common Sidewall Venting - Top View

*Consult the NFPA ANSI Z223.1 Gas Vent
Termination criteria if roof pitch exceeds 9:12.

Rooftop Vent Cap

Roof

Dual Exhaust

Assembly

Heater

Firestop Spacer

Double-Wall B

Vent

24 in.

Min.*

Double-Wall B-Vent

Heater

Heater

Dual Exhaust

Assembly

Sidewall

Sidewall Vent Cap

Wall Thimble

B to C

Adapter

Single Wall Vent

6 in.

Min.

Heater