3.0

Installation

Electrical Requirements

Field Wiring

WARNING

!

Electric Shock
Field wiring to the radiant tube heater must be connected and grounded in accordance
with national, state, provincial and/or local codes. In the United States refer to the most
current revisions to the ANSI/NFPA 70 Standard and in Canada refer to the most current
revisions to the CSA C22.1 Part I Standard.

Wiring

Figure 3.21

Field Wiring Diagram

Multiple Unit operation on a Single 24V Control*

N

L1

N

L1

PANEL

GROUND

120V BLACK

POWER CORD

24V YELLOW
CONTROL
CORD

Low Fire

Common

Common

High Fire

PANEL

GROUND

G

W

BK

G

W

BK

120V BLACK

POWER CORD

24V YELLOW
CONTROL
CORD

Low Fire

High Fire

G

W

BK

G

W

BK

EXTERNAL TRANSFORMER
REQUIRED.
A 40VA TRANSFORMER IS
SUFFICIENT TO OPERATE
UP TO TEN APPLIANCES.

NOTE: STAGE 1 IS THE
HIGHER TEMPERATURE
SETPOINT AND STAGE TWO IS
THE LOWER TEMPERATURE
SETPOINT

24V OUT - STAGE 1

(LOW FIRE)

24V OUT - STAGE 2

(HIGH FIRE)

24V IN

BURNER BOX

24V Yellow Control Cord
Green: Common
White: Low Fire
Black: High Fire

*

NOTE: In order for the unit to operate with this configuration, the

Dual Pole, Dual Throw Switch must be toggled to the 24VAC IN
position. (See Detail ‘A’)

CONTROL VOLTAGE SELEC TOR

24VAC

IN

24VAC

OUT

INSIDE SERVICE PANEL

DETAIL ‘A’

CONTROL VOLTAGE SELECTOR

24VAC

IN

24VAC

OUT