Mod30ml and modcell mlp reference tables – Micromod MOD: MODBUS RTU Communications Guide User Manual

Page 24

background image

MODBUS RTU

COMMUNICATIONS GUIDE

20

MOD30ML AND MODCELL MLP REFERENCE TABLES

Table 11. MOD30ML and Modcell Multiloop Processor to Host Device or PC Sample Configuration Entries

MOD30ML or Modcell Multiloop Processor

Host Device or PC

Signal Source

List

Data

Engineering

Range

Type

Entry

Modbus List

Range

Scale

MSC

Modbus

Data

Device

Range

Engineering

Range

Type

Low

High

CL ML Number Low

High

Factor Connection Address

Type

Low

High

Low

High

Note

Floating

Point

0

100

X

1

0

100

SRWIN1

40001

WORD

0

65535

0

100

Floating

Point

-10

10

X

2

-10

10

SRWIN1

40002

WORD

0

65535 -10

10

Floating

Point

-14

0

X

3

-14

0

SRWIN1

40003

WORD

0

65535 -14

0

Floating

Point

0

80000

X

1

0

8000

SRWIN2

40101

WORD

0

65535

0

8000

10x mult

req’d

mSec

Time

0

4294967295

X

2

0

65535

1 SRWIN2

40102

WORD

0

65535

0

65535 1 mSec /

count

mSec

Time

0

4294967295

X

3

0

65535

10 SRWIN2

40103

WORD

0

65535

0

65535 10 mSec

/ count

mSec

Time

0

4294967295

X

4

0

65535

100 SRWIN2

40104

WORD

0

65535

0

65535

100

mSec /

count

mSec

Time

0

4294967295

X

5

0

65535

1000 SRWIN2

40105

WORD

0

65535

0

65535

1 Sec /

count

mSec

Time

0

4294967295

X

6

0

65535

10000 SRWIN2

40106

WORD

0

65535

0

65535 10 Sec /

count

mSec

Time

0

4294967295

X

7

0

65535 100000 SRWIN2

40107

WORD

0

65535

0

65535 100 Sec

/ count

Discrete

0

1

X

8

SRWIN2

40108

WORD

0

65535

0

1

Bit 1 of

16

Discrete

0

1

X

9

SRWIN2

40109

WORD

0

65535

0

1

Bit 1 of

16

Discrete

0

1

X

1

DRWIN1

00001

BIT

0

1

0

1

Bit 1 of 1

Discrete

0

1

X

2

DRWIN1

00002

BIT

0

1

0

1

Bit 1 of 1

Floating

Point

0

100

X

1

MRWIN1

41001

FLOAT

0

100

0

100

Floating

Point

-10

10

X

2

MRWIN1

41003

FLOAT

-10

10

-10

10

Floating

Point

-14

0

X

3

MRWIN1

41005

FLOAT

-14

0

-14

0

Floating

Point

0

80000

X

1

MRWIN2

41101

FLOAT

0

80000

0

80000

* NOTE:

When connections are made from a source that has a variable data type,
the Range and Scale Factor fields may be enabled when they do not
apply. In this case, leave the default Range of 0 to 65535 and Scale
Factor of 1.