Mod30ml and modcell mlp reference tables – Micromod MOD: MODBUS RTU Communications Guide User Manual
Page 24

MODBUS RTU
COMMUNICATIONS GUIDE
20
MOD30ML AND MODCELL MLP REFERENCE TABLES
Table 11. MOD30ML and Modcell Multiloop Processor to Host Device or PC Sample Configuration Entries
MOD30ML or Modcell Multiloop Processor
Host Device or PC
Signal Source
List
Data
Engineering
Range
Type
Entry
Modbus List
Range
Scale
MSC
Modbus
Data
Device
Range
Engineering
Range
Type
Low
High
CL ML Number Low
High
Factor Connection Address
Type
Low
High
Low
High
Note
Floating
Point
0
100
X
1
0
100
SRWIN1
40001
WORD
0
65535
0
100
Floating
Point
-10
10
X
2
-10
10
SRWIN1
40002
WORD
0
65535 -10
10
Floating
Point
-14
0
X
3
-14
0
SRWIN1
40003
WORD
0
65535 -14
0
Floating
Point
0
80000
X
1
0
8000
SRWIN2
40101
WORD
0
65535
0
8000
10x mult
req’d
mSec
Time
0
4294967295
X
2
0
65535
1 SRWIN2
40102
WORD
0
65535
0
65535 1 mSec /
count
mSec
Time
0
4294967295
X
3
0
65535
10 SRWIN2
40103
WORD
0
65535
0
65535 10 mSec
/ count
mSec
Time
0
4294967295
X
4
0
65535
100 SRWIN2
40104
WORD
0
65535
0
65535
100
mSec /
count
mSec
Time
0
4294967295
X
5
0
65535
1000 SRWIN2
40105
WORD
0
65535
0
65535
1 Sec /
count
mSec
Time
0
4294967295
X
6
0
65535
10000 SRWIN2
40106
WORD
0
65535
0
65535 10 Sec /
count
mSec
Time
0
4294967295
X
7
0
65535 100000 SRWIN2
40107
WORD
0
65535
0
65535 100 Sec
/ count
Discrete
0
1
X
8
SRWIN2
40108
WORD
0
65535
0
1
Bit 1 of
16
Discrete
0
1
X
9
SRWIN2
40109
WORD
0
65535
0
1
Bit 1 of
16
Discrete
0
1
X
1
DRWIN1
00001
BIT
0
1
0
1
Bit 1 of 1
Discrete
0
1
X
2
DRWIN1
00002
BIT
0
1
0
1
Bit 1 of 1
Floating
Point
0
100
X
1
MRWIN1
41001
FLOAT
0
100
0
100
Floating
Point
-10
10
X
2
MRWIN1
41003
FLOAT
-10
10
-10
10
Floating
Point
-14
0
X
3
MRWIN1
41005
FLOAT
-14
0
-14
0
Floating
Point
0
80000
X
1
MRWIN2
41101
FLOAT
0
80000
0
80000
* NOTE:
When connections are made from a source that has a variable data type,
the Range and Scale Factor fields may be enabled when they do not
apply. In this case, leave the default Range of 0 to 65535 and Scale
Factor of 1.