MODBUS RTU

COMUNICATIONS GUIDE

18

MODCELL MLP WITH TCP QUICKPANEL

Table 9. Wiring for RS-485 Full Duplex

QuickPanel jr.

Modcell MLP

TXA

11

—————

29-1

Rx+

TXB

15

—————

29-2

Rx-

RXA

10

—————

30-1

Tx+

RXB

16

—————

30-2

Tx-

Frame Ground

1

— Shield

RTS

4

——

CTS

5

——

CTSB

18

——

DTRB

19

——

CTSA

21

——

DTRA

22

——

PLC & Protocols

SIO/CN1

PLC

Modicon Modbus is used when QuickPanel is Master to MLP

Modicon Modbus Slave is used when QuickPanel is slave to MLP
Port

Electrical Format: RS-422/485 Full duplex
Baud rate, Data bits, Parity and Stop Bits to match the MLP configuration

Handshake: None
Protocol

PLC ID: Modbus address of the MLP

Tags

Analog points are read from the MLP as an integer value (16-bit).
MLP floating-point numbers are not supported by this interface.

Addressing

Registers are referenced as a type and offset. Below are examples for Input Registers and Output (Holding)
Registers.

Table 10. TCP QuickPanel Addressing

ML to MSC SROIN1

Modbus Address

QuickPanel Tag

Entry 1

30001

IR001

Entry 2

30002

IR002

ML to MSC SRWIN1

Entry 1

40001

OR001

Entry 2

40002

OR002

If connecting more than one slave to the QuickPanel, append an underscore and Modbus address to the tag.
Example:

QuickPanel is configured to access PLC ID 1
For MLP at address 2, with the same registers as above, the tags would be IR001_2, IR002_2,
OR001_2 and OR002_2.