MaxPower Corp Toshiba 1600XP Series User Manual
Page 5
5
1600EP Series Instruction Manual Addendum
STANDARD MODELS: 3.6 kVA-C1; 3.6 kVA; 6 kVA; 8 kVA (CONT’D)
Unit (Capacity)
3.6 kVA-C1
(3.1
kW)
1
3.6 kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
Mechanical Design
Enclosure
Enclosure of unit made from sheet metal meeting NEMA1 and UL Type 1
Size (HxWxD) Inches (max)
21 x 10 x 33
27.5 x 10 x 33
28.25 x 13 x 33.5
Paint System
Powder coating
Fan Panel
Panel mounted on back of UPS to allow for
easy replacement of fans without turning off power to UPS
Battery System
Battery Replacement
Slide out battery packs accessible from front of UPS
(Factory or authorized service center serviceable only)
Battery Packs
Designed for battery acid leakage containment with (6) batteries per pack
Battery Pack Size
HxWxD)Inches(max)
5 x 7.3 x 18.2
Battery Pack Quantity
2
3
3
4
Battery Manufacturer
Enersys
Battery Type
NPX-35
Toshiba’s Part Number for
Battery Pack
51896
(1) Input/output
fi gures rated for 240 volts. Output ratings given for 0.85 pF are only valid when the input voltage is
greater than 204 volts; otherwise, ratings given for 0.70 pF are applicable.
(2) Battery backup time may vary depending on the operating conditions and ambient temperature at the installation site.
(3) An initial charge time of 24 hrs. is necessary to obtain proper battery performance level before unit is placed in
operation.
(4) At 6600 ft (2000 m) above sea level, output capacity should be derated by 3%.