UPS Specifi cations
STANDARD MODELS: 3.6 kVA-C1; 3.6 kVA; 6 kVA; 8 kVA
Unit (Capacity)
3.6 kVA-C1
(3.1 kW)
1
3.6 kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
General
Topology
True On-line
Certifi cations
UL, CUL, ISO 9001, NEMA/PE1-1993
Input Characteristics
Input Voltage
Single-phase, 208/240 Vac, -30% – +10%
Input Frequency
45 – 65 Hz (auto-sensing)
Input Capacity
3.6 kVA
6.0 kVA
8.0 kVA
Input Power Factor
> 0.95 for all loads
Current THD (linear load)
< 5% total harmonic distortion
Included AC Input Breaker
Rating
30 A/277 V
50 A/277 V
60 A/277 V
Battery Characteristics
Battery Type
Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged
@ 0.7 power factor, 77 °F
8 min.
minimum
2
14 min.
minimum
2
7 min.
minimum
2
Backup time, fully charged
@ 0.85 power factor, 77 °F
7 min.
minimum
2
10 min.
minimum
2
7 min.
minimum
2
Recharge Time
24 hr. (full), 12 hr. (90%) for internal batteries only
3
Battery Voltage (Nominal)
144 Vdc
216 Vdc
216 Vdc
288 Vdc
Output Characteristics
Output Voltage
Single-phase, 240/208/120 V
Output Voltage Regulation
± 3%
Output Frequency
±0.5 Hz/1 Hz/1.5 Hz (factory or authorized service center selectable only)
AUTO/MAN Frequency
Factory or authorized service center selectable only
Voltage THD
< 3% for linear load; < 6% for non-linear load
Common-Mode Noise
< 0.5Vrms
Rated Load Power Factor
0.85 (0.6 – 1.0) lagging
Effi ciency (ac-dc-ac)
> than 83% (without battery charge)
Voltage Transient
< ±8% (Load of 0 – 100 %)
Rated Output Current (rms)
15 A
25 A
33.3 A
Max. Peak Output Current
45 A
75 A
100 A
Inverter Overload Capacity
125% for 30 sec./150% for 10 sec.
Bypass Overload Capacity
125% for 10 min./1000% for 1 cycle