General technical data
Power supply range*
19.2 to 30VDC
Bridge voltage supply
Bus connectors (Power-Bus) can be snapped onto
35mm DIN rail guide according to EN 60715
Wire section
0.2 to 2.5mm
2
Wire stripping
0.3 in (8mm)
Hot swapping
Yes
Max current consumption
21 to 25mA (24VDC)
Consumption without load at 25°C
7.5mA
Max power consumption
500mW
A/D conversion
14-bit
Rejection
50 or 60Hz (programmable)
Settings
Dip-switch
Filter
Settable
Dimensions
3.67 x 0.24 x 4.04 in (93.1 x 6.2 x 102.5mm)
Isolation
1.5kV (50 or 60Hz, 1 min)
Isolation technique
Digital (optocoupler)
Processing
Floating point 32-bit
Color
Black
Case material
PBT
Weight
1.6 oz (45g)
Operating temperature
–20°C to +65°C
Storage temperature
–40°C to +85°C
Humidity
10 to 90% noncondensing
Connection
Clamp terminals and/or bus
Protection degree
IP20
* Except for DSCP55 and DSCP70
Dimensions
Cage clamp connection
Power-Bus
Connection
sequence requires
stripping of cables,
opening block
spring with a
screwdriver, and
inserting the cable
into the hole.
Each expandable
Power-Bus
connector allows
insertion of
two modules.
Insert Power-
Bus connectors
into DIN rail
by attaching
to upperside
and rotating
downward.
0.2 to 2.5mm
2
8mm
3.67“ (93.1mm)
4.04
“ (102.5mm)
0.24“
(6.2mm)
DSCP55
DSCP61
DSCP62
DSCP63
DSCP64
DSCP65
DSCP70
Function
Pt100, Ni100/loop-powered
converter
Pt100-to-DC current/voltage
converter
Thermocouple-to-DC current/
voltage converter with relay
output
DC voltage/current converter
DC voltage/current converter
with transducer power supply
DC low voltage converter
Power supply connection
module for DIN rail power bus
Functional
diagram
General data
Channels
1 input, 1 output
1 input, 1 output
1 input, 2 outputs
1 input, 1 output
1 input, 1 output
1 input, 1 output
2 inputs, 1 output
Accuracy (max)
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
Thermal drift
<100ppm/°K
<100ppm/°K
<120ppm/°K
<120ppm/°K
<120ppm/°K
<120ppm/°K
LED
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Input/output out of range
• Internal fault
• Dip-switch error
• Input/output out of range
• Internal fault
• Input over-range
• Input 1 correct input V
• Input 2 correct input V
• Reversed inputs or AC
Power supply
Loop powered (5 to 30VDC)
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
Isolation
–––
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
Special functions
• RTD type/connection
• Programmable fault and cut-off
• Filter
• Signal inversion
• Programmable fault and
cut-off
• Filter
• Programmable fault and
cut-off
• Filter
• Settable rejection 50-60Hz
• Square root extraction
• Standard tank linearization
• Signal inversion
• Programmable cut-off
• Square root extraction
• Standard tank linearization
• Signal inversion
• Programmable cut-off
• Transducer power supply
17 to 21V, current 25mA (max)
• Programmable fault
and cut-off
• Filter
• Settable rejection 50-60Hz
• Differential mode filter
• Integrated protection against
overvoltages
• Connection with redundant
power supplies
Input data
Type
Pt100
• EN 60751
• Range: –200°C to +650°C
• Minimum span: 20°C
• Connection technique:
2-, 3-, 4-wire
Ni100
• Range: –60°C to +250°C
• Minimum span: 20°C
• Connection: 2-, 3-, 4-wire
Pt100
• EN 60751
• Range: –150°C to +650°C
• Minimum span: 50°C
• Power on transmitter: 900µA
• Connection: 2-, 3-, 4-wire
• Conductor resistance:
20Ω (max)
Thermocouple
• Type: J, K, E, N, S, R, B, T (ITS-
90 standard)
• Minimum span: 100°C
• Impedance: 10MΩ
• Cold junction
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5, 0 to 15,
0 to 30V
• Impedance: 110kΩ (10V),
325kΩ (30V)
Current
• Range: 0 to 20, 4 to 20mA
• Impedance: 35Ω
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Impedance: 110kΩ
Current
• Range: 0 to 20, 4 to 20mA
• Impedance: 35Ω
Voltage
Programmable ranges:
from ±25 to ±2000mV
Power supply
• Provides connection of single
or redundant external power
supplies
• Positive inputs need protection
by an external fuse of
recommmended sizing
Input (max)
32V (max)
30V or 50V (max)
32V (max)
50V (max)
Output data
Type
Current
• Range: 4 to 20, 20 to 4mA
(2-wire)
Load resistance: 1kΩ
(nominal), 1.2kΩ (max)
• Current: 30mA (max)
Voltage
• Range: 0 to 10, 10 to 0,
0 to 5, 1 to 5V
• Voltage: over-range 10.25 V, or
10.5V (max)
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Current: over-range 20.5mA,
or 21mA (max)
• Load resistance: 500Ω (max)
Voltage
• Range: 0 to 10, 10 to 0,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Current: 25mA (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
•Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Current: 25mA (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Protection: 25mA
Power supply
Max voltage drop: 300mV
Static relay
auxiliary output
• Nominal voltage: 24V AC/DC
• Current: 60mA
• Overvoltage protection: 50V
• Settable alarm trip/hysteresis
Response time
(10-90%)
<220ms (without filter)
<620ms (with filter)
<50ms (without filter)
<200ms (with filter)
<25ms (without filter)
<55ms (with filter)
<35ms (without filter)
<74ms (with filter)
<35ms (without filter)
<74ms (with filter)
<23ms (without filter)
<51ms (with filter)
D/A conversion
Resolution
1µA (>14-bits)
14-bit
14-bit
14-bit
14-bit
14-bit
mA
V
V
VDC
V
mV
V