General data, Input data, Output data – Impulse DSCP55 User Manual
Page 2
![background image](/manuals/335814/2/background.png)
DSCP55
DSCP61
DSCP62
DSCP63
DSCP64
DSCP65
DSCP70
Function
Pt100, Ni100/loop-powered
converter
Pt100-to-DC current/voltage
converter
Thermocouple-to-DC current/
voltage converter with relay
output
DC voltage/current converter
DC voltage/current converter
with transducer power supply
DC low voltage converter
Power supply connection
module for DIN rail power bus
Functional
diagram
General data
Channels
1 input, 1 output
1 input, 1 output
1 input, 2 outputs
1 input, 1 output
1 input, 1 output
1 input, 1 output
2 inputs, 1 output
Accuracy (max)
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
±0.1%
Thermal drift
<100ppm/°K
<100ppm/°K
<120ppm/°K
<120ppm/°K
<120ppm/°K
<120ppm/°K
LED
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Dip-switch error
• Connection error
• Internal fault
• Input/output out of range
• Internal fault
• Dip-switch error
• Input/output out of range
• Internal fault
• Input over-range
• Input 1 correct input V
• Input 2 correct input V
• Reversed inputs or AC
Power supply
Loop powered (5 to 30VDC)
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
19.2 to 30VDC
Isolation
–––
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
1.5kV (50 or 60Hz,1 min)
Special functions
• RTD type/connection
• Programmable fault and cut-off
• Filter
• Signal inversion
• Programmable fault and
cut-off
• Filter
• Programmable fault and
cut-off
• Filter
• Settable rejection 50-60Hz
• Square root extraction
• Standard tank linearization
• Signal inversion
• Programmable cut-off
• Square root extraction
• Standard tank linearization
• Signal inversion
• Programmable cut-off
• Transducer power supply
17 to 21V, current 25mA (max)
• Programmable fault
and cut-off
• Filter
• Settable rejection 50-60Hz
• Differential mode filter
• Integrated protection against
overvoltages
• Connection with redundant
power supplies
Input data
Type
Pt100
• EN 60751
• Range: –200°C to +650°C
• Minimum span: 20°C
• Connection technique:
2-, 3-, 4-wire
Ni100
• Range: –60°C to +250°C
• Minimum span: 20°C
• Connection: 2-, 3-, 4-wire
Pt100
• EN 60751
• Range: –150°C to +650°C
• Minimum span: 50°C
• Power on transmitter: 900µA
• Connection: 2-, 3-, 4-wire
• Conductor resistance:
20Ω (max)
Thermocouple
• Type: J, K, E, N, S, R, B, T (ITS-
90 standard)
• Minimum span: 100°C
• Impedance: 10MΩ
• Cold junction
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5, 0 to 15,
0 to 30V
• Impedance: 110kΩ (10V),
325kΩ (30V)
Current
• Range: 0 to 20, 4 to 20mA
• Impedance: 35Ω
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Impedance: 110kΩ
Current
• Range: 0 to 20, 4 to 20mA
• Impedance: 35Ω
Voltage
Programmable ranges:
from ±25 to ±2000mV
Power supply
• Provides connection of single
or redundant external power
supplies
• Positive inputs need protection
by an external fuse of
recommmended sizing
Input (max)
32V (max)
30V or 50V (max)
32V (max)
50V (max)
Output data
Type
Current
• Range: 4 to 20, 20 to 4mA
(2-wire)
Load resistance: 1kΩ
(nominal), 1.2kΩ (max)
• Current: 30mA (max)
Voltage
• Range: 0 to 10, 10 to 0,
0 to 5, 1 to 5V
• Voltage: over-range 10.25 V, or
10.5V (max)
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Current: over-range 20.5mA,
or 21mA (max)
• Load resistance: 500Ω (max)
Voltage
• Range: 0 to 10, 10 to 0,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Current: 25mA (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
•Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Current: 25mA (max)
Voltage
• Range: 0 to 10, 2 to 10,
0 to 5, 1 to 5V
• Load resistance: 2kΩ (min)
Current
• Range: 4 to 20, 20 to 4,
0 to 20, 20 to 0mA
• Load resistance: 500Ω (max)
• Protection: 25mA
Power supply
Max voltage drop: 300mV
Static relay
auxiliary output
• Nominal voltage: 24V AC/DC
• Current: 60mA
• Overvoltage protection: 50V
• Settable alarm trip/hysteresis
Response time
(10-90%)
<220ms (without filter)
<620ms (with filter)
<50ms (without filter)
<200ms (with filter)
<25ms (without filter)
<55ms (with filter)
<35ms (without filter)
<74ms (with filter)
<35ms (without filter)
<74ms (with filter)
<23ms (without filter)
<51ms (with filter)
D/A conversion
Resolution
1µA (>14-bits)
14-bit
14-bit
14-bit
14-bit
14-bit
mA
V
+DC
VDC
mA
V
mA
V
mA
V
mA
mA
V
VDC
VDC
VDC
mA
V
Pt100
Ni100
Pt100
TC