Smart-UPS 2200/3000 VA 100/120/230 VAC Tower User Manual

9

Configuration

Configuration

UPS settings

Settings are adjusted through PowerChute software or optional Smart Slot accessory cards.

Function

Factory

Default

User Selectable

Choices

Description

Automatic

Self-Test

Every 14 days

(336 hours)

• Every 7 days

(168 hours)

• On start up only
• No self-test

Set the interval at which the UPS will execute a

self-test.

UPS ID

UPS_IDEN

Up to eight characters

(alphanumeric)

Uniquely identify the UPS, (i.e. server name or

location) for network management purposes.

Date of Last

Battery

Replacement

Manufacture

Date

mm/dd/yy

Reset this date when you replace the battery

module.

Minimum Capacity

Before Return from

Shutdown

0 percent

• 0%
• 15%
• 30%
• 45%

• 50%
• 60%
• 75%
• 90%

Specify the percentage to which batteries will

be charged following a low battery shutdown

before powering connected equipment.

Voltage Sensitivity
The UPS detects

and reacts to line

voltage distortions
by transferring to

battery operation to

protect the
connected

equipment.

High sensitivity

Brightly
illuminated: high

sensitivity
Dimly illuminated:
medium sensitivity
No illumination:

low sensitivity

Adjust by pressing the VOLTAGE SENSITIVIY

switch

(rear panel). Use a pointed object,

(such as a pen) to do so.
Note: In situations of poor power quality, the

UPS may frequently transfer to battery

operation. If the connected equipment can
operate normally under such conditions, reduce

the sensitivity setting to conserve battery

capacity and service life.

Alarm Delay

Control

Enable

• Enable
• Mute
• Disable

Mute ongoing alarms or disable all alarms

permanently.

Shutdown Delay

90 seconds

• 0 s
• 90 s
• 180 s
• 270 s

• 360 s
• 450 s
• 540 s
• 630 s

Set the interval between the time when the UPS

receives a shutdown command and actual

shutdown.