Smart-UPS 2200/3000 VA 100/120/230 VAC Tower User Manual

Configuration

Low Battery
Warning

2 minutes

PowerChute

software
interface

provides

automatic,
unattended

shutdown when

approximately
two minutes of

battery operated

run time
remains.

Brightly
illuminated:

low battery warning

level of about 2 minutes

Dimly illuminated:
low battery

warning level of about
5 minutes

No illumination:
low battery warning

level is about 8 minutes

The low-battery warning beeps are continuous
when two minutes of run time remain.
To change the default interval setting, use a

pointed object such as a pen to press the

VOLTAGE SENSITIVIY switch

(rear

panel), while

pressing the

button, (front display).

Change the low battery warning interval setting

to the time that the operating system or system

software requires to safely shut down.

Synchronized

Turn-on Delay

0 seconds

• 0 s
• 60 s
• 120 s
• 180 s

• 240 s
• 300 s
• 360 s
• 420 s

Specify the time the UPS will wait after the

return of utility power before start up, (to avoid
branch circuit overload).

High Transfer Point

100 V models:

108 VAC

120 V models:

127 VAC

230 V models:

253 VAC

• 108 VAC
• 110 VAC

• 127 VAC
• 130 VAC

• 253 VAC
• 257 VAC

• 112 VAC
• 114 VAC

• 133 VAC
• 136 VAC

• 261 VAC
• 265 VAC

To avoid unnecessary use of the battery where

utility voltage is chronically high, set the high
transfer point higher if the connected

equipment can tolerate this condition.

Low Transfer Point

100 V models:
92 VAC

120 V models:
106 VAC

230 V models:
208 VAC

• 86 VAC
• 88 VAC

• 97 VAC
• 100 VAC

• 196 VAC
• 200 VAC

• 90 VAC
• 92 VAC

• 103 VAC
• 106 VAC

• 204 VAC
• 208 VAC

To avoid unnecessary use of the battery where
utility voltage is chronically low, set the low

transfer point lower if the connected equipment

can tolerate this condition.

Output Voltage
230 V models

230 VAC

• 220 VAC

• 240 VAC

230 V models only: Sets the output voltage of
the UPS.

Function

Factory

Default

User Selectable

Choices

Description