Smart-UPS 2200/3000 VA 100/120/230 VAC Tower User Manual

Start Up

Connect the UPS to the Network (if Applicable)

Communication Ports

Emergency Power Off

The emergency power off (EPO) feature is user configurable. EPO provides immediate de-energizing of

connected equipment from a remote location, without switching to battery operation.

1. Use the EPO connector supplied with the UPS.
2. Use a normally-open contact to connect the +24 terminal to the IN terminal.
3. Wire the four-pin connector to the EPO system.

The EPO interface is a Safety Extra Low Voltage (SELV) circuit. Connect it only to other SELV

circuits. The EPO interface monitors circuits that have no determined voltage potential. Such closure

circuits may be provided by a switch or relay properly isolated from the utility. To avoid damage to the

UPS, do not connect the EPO interface to any circuit other than a closure type circuit.

Use one of the following cable types to connect the UPS to the EPO switch.

CL2: Class 2 cable for general use.

CL2P: Plenum cable for use in ducts, plenums, and other spaces used for environmental air.

CL2R: Riser cable for use in a vertical run in a floor-to-floor shaft.

CLEX: Limited use cable for use in dwellings and for use in raceways.

For installation in Canada: Use only CSA certified, type ELC, (extra-low voltage control cable).

For installation in other countries: Use standard low-voltage cable in accordance with national and

local regulations.

SERIAL PORT

USB PORT

120/230 V models: Use only the supplied cable to connect to the serial

port. A standard serial interface cable is incompatible with the UPS.
100 V models:
Users may purchase software and cables as an

accessory to the UPS. Refer to the APC Web site, www.apc.com for

information on accessories.
Serial and USB ports cannot be used simultaneously.

EPO PORT

(located on rear panel)

EPO

Connector