American Power Conversion 2200 VA User Manual
Page 14
14
Smart-UPS 2200/3000 VA 100/120/230 VAC Tower User Manual
Troubleshooting
There is no utility power
There is no utility power and the UPS is
off.
120/230 V models: Use the cold start feature to supply power to the
connected equipment front the UPS battery(s).
Press the
button for one second and release. The UPS will beep briefly.
Press and hold the
button again for about three seconds. The unit will
emit two beeps. Release the button during the second beep.
UPS operates on battery although line voltage exists
The UPS input circuit breaker trips.
Unplug all nonessential equipment from the UPS.
Reset the circuit breaker.
Your system is experiencing very high,
low or distorted line voltage.
Move the UPS to a different outlet on a different circuit: Inexpensive fuel
powered generators may distort the voltage. Test the input voltage with the
utility voltage display, (see Operation). If acceptable to the connected
equipment, reduce the UPS sensitivity.
Battery Charge and Load LEDs flash simultaneously
The UPS has shut down.
The internal temperature of the UPS has
exceeded the allowable threshold for
safe operation.
Check that the room temperature is within the specified limits for operation.
Check that the UPS is properly installed, allowing for adequate ventilation.
Allow the UPS to cool down. Restart the UPS. If the problem persists,
contact APC at www.apc.com.
Diagnostic utility voltage
All five LEDs are illuminated.
The line voltage is extremely high and should be checked by an electrician.
There is no LED illumination.
The line voltage is extremely high and should be checked by an electrician.
On Line LED
There is no LED illumination.
The UPS is running on battery, or it must be turned on.
The LED is blinking.
The UPS is running an internal self-test.
Problem and/or Possible Cause
Solution