beautypg.com

39 start stop batch, Se 56 – Burkert Type 8056 User Manual

Page 39

background image

SE 56

39

START STOP BATCH

START: it is possible to activate the start of batch in two different ways:

1.

From remote input: assigning the functions of start/stop batch to the input 1 (pos. 5.9)
or input 2 (pos. 5.10) and using the inputs like visualized from page 14.

2.

From keyboard: short pressing of the key

N.B.: The start of batch from keyboard is always initiated on the release of the key. The
function is not available with the batch consent (pos. 12.7) function enabled.

STOP: A batch may stop (be stopped) due to three events:

1.

Keyboard or remote input (manual stop): short pressing of the key

2.

End of batch: In this case the batch will be stopped once the batch quantity has been
achieved and a signal given

3.

Maximum time of batch: If a maximum batch time has been set, and is exceeded, the
batch in progress is stopped independently from the batched quantity.


Notes:

‰

during the batch the symbol of the active batch and the name of the formula are
visualized on display.


‰

When the batch outputs are enabled, pushing the key

for more than 5 seconds will

energize the outputs until the key is released. On the display, In place of the CT and ST
totalizers the following message will appear:

!! VALVE !!
!! OPENED !!

















IMPORTANT NOTES

The start of the batch disables any function listed in the table below:


* If using Input 1
** Value set to zero

POS 12.5

POS 12.6

POS 5.6

POS 12.1

POS 5.9

POS 3.5-5.8

POS 3.6

POS 5.7

A

U

TO

B

A

TC

H

BM AUT

O

S

E

L

BL

OC

K TOT

A

L

IZER

N. S

A

MPL

E

S

IN

PU

T 1

O

N

S

TA

R

T/

S

T

O

P

BATCH

AUT

O

RA

NGE

CH

AN

GE

OR

FR

OM I

N

P

U

T

EN

ER

GY SAVI

N

G

CAL

IBR

ATI

O

N

POS 12.5

AUTO BATCH

*DISABLE

POS 12.6

BM AUTO SEL

** DISABLE

POS 12.7

CONS. MODE

DISABLE

DISABLE

* DISABLE

POS 5.9

INPUT 1 ON START/STOP
BATCH

DISABLE

DISABLE

DISABLE

POS 5.10

INPUT 2 ON START/STOP
BATCH

DISABLE

DISABLE

DISABLE

DISABLE

POS 5.10

INPUT 2 on BM SELECT

DISABLE

** DISABLE

POS 6.1-4

OUTPUT ON END BATCH

DISABLE


To optimize the performances of the meter used as a batch instrument (batch time < 5s), it is
recommended to set it as prompt as possible according to the plant requirements, choosing the
batching setup for the automatic parameter optimization of the quick start menu. It is also
reccomended to disactivate the function 3.1, AC filter.

This manual is related to the following products: