Burkert Type 8056 User Manual
Page 34
SE 56
34
FUNCTIONS FOR INPUT 2
OFF: DISABLE
T+ RESET: RESET TOTAL DIRECT TOTALIZER FOR DIRECT FLOW RATE (+)
P+ RESET: RESET PARTIAL DIRECT TOTALIZER FOR DIRECT FLOW RATE (+)
T- RESET: RESET TOTAL REVERSE TOTALIZER FOR REVERSE FLOW RATE (-)
P- RESET: RESET PARTIAL REVERSE TOTALIZER FOR REVERSE FLOW RATE (-)
BATCH: START/STOP BATCH
BM SELECTION: STATIC SELECTION OF FORMULA
MENU 5 - INPUTS
(POS. 5.1-4) Reset totalizer enable
[T/P+/-RESET=ON/OFF]
When one of this function is enabled, the related totalizer may be reset through the on/off input.
(POS. 5.7) “Block measures” command block measures enable
[Meas. lock=ON/OFF]
When this function is active (ON), applying a voltage on the on input terminals, the measurement is
stopped, the meter will display zero flow.
(POS. 5.8) “Autozero” calibration external command enable
[Calibration=ON/OFF]
When this function is active, applying a voltage on the on/off input terminals the meter performs a
autozero calibration cycle. ATTENTION: If the voltage pulse is less than 1 sec., the meter performs a
calibration cycle to for compensate possible thermal drifts. If the voltage pulse is more than 1 sec, the
meter performs a zero calibration measure. This function enables/disables the automatic zero
calibration of the system. To perform the calibration it is absolutely necessary for the sensor to be full
of liquid and that the liquid is perfectly staying still. Even very small movement of the liquid may
affect the result of the calibration, and, consequently, the accuracy of the system.
(POS. 5.11) Functions assigned to input 2 [Inp.2=XXXXXX]
Allows to choose the function associated to input 2. The functions are listed in the table below.
MENU 6 - OUTPUTS
(POS. 6.1-4) Function corresponding to on/off output 1-2-3-4
[OUT1=XXXXXX]
Choice of the function corresponding to digital outputs. The functions are listed in the table below.
The output 3-4 are optional and the output 4 is the only output, which can reach a 12.5
kHz frequency.
FUNCTIONS ASSOCIATED TO THE OUTPUTS 1, 2, 3, 4
OFF: DISABLED
#1 IMP+: PULSE ON CHANNEL 1 FOR POSITIVE FLOW RATE
#1 IMP-: PULSE ON CHANNEL 1 FOR NEGATIVE FLOW RATE
#1 IMP: PULSE ON CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE
#2 IMP+: PULSE ON CHANNEL 2 FOR POSITIVE FLOW RATE
#2 IMP-: PULSE ON CHANNEL 2 FOR NEGATIVE FLOW RATE
#2 IMP: PULSE ON CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE
#1 FREQ+: FREQUENCY CHANNEL 1 FOR POSITIVE FLOW RATE
#1 FREQ-: FREQUENCY CHANNEL 1 FOR NEGATIVE FLOW RATE
#1 FREQ: FREQUENCY CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE
#2 FREQ+: FREQUENCY CHANNEL 2 FOR POSITIVE FLOW RATE
#2 FREQ-: FREQUENCY CHANNEL 2 FOR NEGATIVE FLOW RATE
#2 FREQ: FREQUENCY CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE
SIGN: FLOW DIRECTION OUTPUT (ENERGIZED = -)
RANGE: RANGE INDICATION OUTPUT (ENERGIZED = SCALE 2)
MAX AL.+: MAX DIRECT FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX AL.-: MAX REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX AL.: MAX DIRECT/REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL.+: MIN DIRECT FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL.-: MIN REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MIN AL.: MIN DIRECT/REVERSE FLOW RATE OUTPUT(ENERGIZED = AL. OFF)
MAX+MIN: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGIZED = AL. OFF)
P. EMPTY: EMPTY PIPE ALARM OUTPUT (ENERGIZED = FULL PIPE)
OVERFLOW: OUT OF RANGE ALARM OUTPUT (ENERGIZED = FLOW RATE OK)
HARDW AL.: CUMULATIVE ALARM OUTPUT interrupt coils, empty pipe, measure error (ENERGIZED = NO ALARMS
BATCH AL.: BATCH ALARM
EXT. COMM.: ONLY AVAILABLE WITH DATA LOGGER MODULE
BATCH SYN.: AT THE AND OF BATCH THE OUTPUT CHANGE STATUS
END BATCH.: END BATCH OUTPUT (ENERGIZED =BATCH IN PROGRESS)
PREBATCH.: PREBATCH OUTPUT (ENERGIZED = PREBATCH IN PROGRESS)