beautypg.com

7assembly and fluidic installation, 4 electrical data, English – Burkert Type 8030 User Manual

Page 7

background image

7

Technical data

type se30 ex

H

DN (mm)

H (mm)

06

96

08

96

15

101

20

98

25

98

32

102

40

106

50

112

65

112

Fig. 4:

Dimension H of the device with a female connector type 2513,
available as an accessory, and mounted on a fitting S030

H

DN (mm)

H (mm)

15

1)

101

25

116

40

133

50

151

1)

Only version with internal thread

connections

Fig. 5:

Dimension H of the device with a female connector type 2513,
available as an accessory, and mounted on a fitting S070

6.4 electrical data

Power supply

U. 12-36 VDC, filtered and regulated

Consumption (without load) Imax. ≤ 30 mA

Reversed polarity

protected

Protection against spike
voltages

protected

Protection against short
circuits

protected

Transistor outputs

1 x NPN and 1 x PNP, Imax. < 100 mA, fre-
quency 0 to 300 Hz with duty cycle of 1/2

7

Assembly AnD fluIDIc
InstAllAtIon

Do the fluidic installation and the assembly as described in the
operating instructions type 8030 provided with the device.

English