beautypg.com

Flowline LC30 Thermo-Flo User Manual

Page 6

background image

6 of 14 

LC900008 

Rev A

GETTING STARTED 

Step Four 

The  LC30  Series  may  be  used  with  any  Flowline  flow  switch  with  an  N‐channel  (ends  in  “‐_  _  _  2”)  or  relay 
(ends  in  “‐_  _  _  5”)  output.    The  relay  is  a  single  pole,  double  throw  type;  the  controlled  device  can  be 
connected to either the normally open or normally closed side of the relay.  A time delay from 0 to 60 seconds 
can be set before the relay responds to the sensor input.  Typical applications for the LC30 Series are pump 
protection, no‐flow indication or chemical injection. 

Guide to Controls:  Below is a listing and the location of the different components for the controller: 

Standard Version (Non‐CE) 

CE Version (LC30‐10_1‐CE / LC30‐10_1‐E‐CE) 

 

 

1. Power indicator:  This green LED lights when AC power is ON.   

2. Relay  indicator:    This  red  LED  will  light  whenever  the  controller  energizes  the  relay,  in  response  to  the 

proper condition at the sensor input and after the time delay.   

3. AC Power terminals:  Connection of 120 VAC power to the controller.  The setting may be changed to 240 

VAC if desired.  This requires changing internal jumpers; this is covered in the Installation section of the 
manual. Polarity (neutral and hot) does not matter. 

4. Relay  terminals  (NC,  C,  NO):    Connect  the  device  you  wish  to  control  (pump,  alarm  etc.)  to  these 

terminals: supply to the COM terminal, and the device to the NO or NC terminal as required.  The switched 
device should be a non inductive load of not more than 16 amps; for reactive loads the current must be 
derated or protection circuits used.  When the red LED is ON and the relay is in the energized state, the NO 
terminal will be closed and the NC terminal will be open. 

5. Invert  switch:    This  DIP  switch  reverses  the  logic  of  the  relay  control  in  response  to  the  sensor(s): 

conditions that used to energize the relay will make it turn off and vice versa. 

6. Time Delay:  After the input(s) change(s) state, this control sets a delay from 0.15 to 60 seconds before the 

relay will respond.  

7. Input 1A indicator:  These amber LED will light immediately whenever the appropriate sensor attached to 

the  terminals  detects  no‐flow,  and  will  turn  off  when  it  detects  flow.    This  polarity  can  be  reversed  by 
change of the switches polarity. 

8. Input terminals:  Connect the wiring from the sensors to  these terminals: Note the polarity:  (+) is a 24 

VDC,  100  mA  power  supply  (to  be connected  to  the  red  wire  of  a  Flowline  sensor),  and  (‐)  is  the  return 
path from the sensor (to be connected to the black wire of a Flowline sensor).  (S) is the relay signal input 
to be connected to the white wire.  The remaining green wire will return to the (‐) terminal.  If polarity is 
reversed, the sensors will not work.