beautypg.com

Flowline LC30 Thermo-Flo User Manual

Page 3

background image

Rev A 

LC900008 

3 of 14 

SPECIFICATIONS/DIMENSIONS 

Step Two 

Controller 
Supply voltage: 

120 / 240 VAC, 50 ‐ 60 Hz. 

Consumption: 

5 Watts max. 

Sensor inputs: 

(1) flow switch 

Sensor supply: 

24 VDC @ 50 mA 

LED indication: 

Sensor, relay & power status 

Contact type: 

(1) SPDT Relay 

Contact rating: 

250 VAC, 16A 

Contact output: 

Selectable NO or NC 

Contact delay: 

0 to 60 seconds 

Electronics temp.: 

F: ‐40°to 158° 

 

C: ‐40°to 70° 

Enclosure rating: 

NEMA 4X (IP65) 

Enclosure material: 

PP (U.L. 94 VO) 

Enclosure mount.: 

3/4” NPT (Rc) 

Enclosure rotation: 

300°swivel base 

Conduit entrance: 

Single, 1/2" NPT 

Classification: 

General purpose 

Certificate number: 

LR 79326‐3 

CE compliance: 

EN 61326 EMC 

 

EN 61010‐1 Safety 

Strobe Alert 
Flash type: 

Xenon tube 

Flash frequency: 

1 per second 

Strobe life: 

10M cycles 

Supply voltage: 

120 VAC, 50‐60 Hz. 

Consumption: 

3 Watts max. 

Material: 

Polycarbonate 

Enclosure rating: 

NEMA 4X (IP65) 

Color: 

Amber 

Terminal Labels: 
(S) terminal: 

Provides 14 VDC to the switch input 

(‐) terminal:  

Ground 

(+) terminal: 

Provides 24 VDC power to the switch 

Side View 

(LC30‐1001 & LC30‐1051) 

 

 

Side View with Strobe Alert 

(LC30‐1002 & LC30‐1052) 

LC30 Series 

Functional Diagram