beautypg.com

Flowline LC30 Thermo-Flo User Manual

Page 10

background image

10 of 14 

LC900008 

Rev A

INSTALLATION (continued) 

Step Six 

4. Mechanical connection to conduit:  All wiring between a controller and sensors should be in conduit.  

The power entrance of the controller is a standard ½” NPT female fitting that will attach to standard 
electrical conduit, either plastic or metal, as specified by local codes.  Keep in mind that the housing 
may have to be unscrewed from the sensor for periodic cleaning of the sensor.  For this reason the use 
of flexible conduit, providing enough slack for easy access is recommended. 

5. Connect the extension wiring: 

Before making connections, make sure all power to the system (controller, motor, valve, alarm, etc.) 
is OFF with a safety lockout on the circuit breaker. 

a. The extension wiring to controller should take into account long cable runs.  If the run is long, it 

may need to be a slightly thicker gauge so the series resistance is kelp within allowable limits. 

b. Thread the extension wiring through the power conduit entrance of the housing. 
c. Strip ¼” of the insulation from the ends of the wires. 
d. Loosen  the  appropriate  terminal  screws.    Insert  the  extension  wires  into  the  corresponding 

terminals, matching the sensor wires. 

e. Tighten the terminal screws. 
f. Return  the  wire  protector  to  its  location  and  restore  the  final  screw  which  holds  the  wire 

protected and PCB in its place. 

g. Replace the cap. 

Note: In some cases, additional user‐provided components may need to be attached to the terminals.  If 
so, make sure that both wires and/or components entering the terminal are secure after the screws are 
tightened. 

Note:  Always tighten the controller from the wrench flat located on the 
swivel base. Never tighten from the body of the controller.