beautypg.com

Flowline LC30 Thermo-Flo User Manual

Page 11

background image

Rev A 

LC900008 

11 of 14 

APPLICATION EXAMPLES 

Step Seven 

Low Flow Alarm:  The goal is to indicate when the flow rate falls below a certain point. If it does, an alarm is 
supposed to sound, alerting the operator of a low flow condition. 

If power is accidentally cut to the controller, the sensor's ability to notify the operator of a low flow condition 
could be lost. The system must alert the operator not only to low flow, but to controller power loss. 

To do this, connect the hot lead of the alarm to the NC side of the relay terminal of the controller.  If power is 
lost, the relay will be de‐energized, and the alarm will sound (if there is still power to the alarm circuit itself).  
The  alarm  circuit  should  have  a  noninterruptible  power  supply  or  some  other  indicator  or  backup  alarm  to 
warn of a power failure in the alarm circuit.   

In  this  application,  the  normal  status  is  when  the  sensor  is  in  the  flow  condition,  and  the  relay  will  be 
energized holding the alarm circuit open.  Please note that the flow switch can be wired either normally closed 
or normally open (Step 5). When the switch is wired NC, the input LED will be off and the relay LED will be on. 
So for this application, Invert should be set to the On position.  When the switch is wired NO, the input LED 
and the relay LED will be on simultaneously.  So for this application, Invert should be set to the Off position. 

LED Indication:  Use LED's located above the input terminals to indicate whether the switch is in a flow or no‐
flow  state.  When  the  switch  is  wired  NC,  Amber  indicates  no‐flow  and  Off  indicates  flow.  Reversing  the 
polarity (Normally Open), Amber indicates flow and Off indicates no‐flow. 

Normally Closed (NC) 

Amber LED ON for No‐Flow 

Normally Closed (NC) 

LED OFF for Flow 

Normally Open (NO) 

Amber LED ON for Flow 

Normally Open (NO) 

LED OFF for No‐Flow 

 

Flow Switch LED ON 

for No‐Flow 

 

Flow Switch LED OFF 

for Flow 

 

Flow Switch LED OFF 

for Flow 

 

Flow Switch LED ON 

for No‐Flow 

Note: The LED inside the flow switch will always be ON for No‐Flow and OFF for Flow, regardless of the polarity 
of the flow switch.  In NC wiring, the switch’s LED will match the controller’s LED.  In NO wiring, the switch’s 
LED will be opposite of the controller’s LED.