beautypg.com

DE DIETRICH NEO 2.1 User Manual

Page 70

background image

To prevent damage to the collectors and their connections by frost

and corrosion, it is essential that a high quality heat transporting fluid

be used to fill the solar installation. Use of the heat transporting fluid

that we propose provides good anti-frost protection down to

approximately -24°C.

To prevent any damage of the system, pressure tests should only

be carried out with the heat-transporting fluid used later on.

4

Testing pressure: 4 bar

4

Test time: minimum 1 hour

4

Pressure gauge

39

Filling pump

61

Thermometer

84

Stop valve with releasable non-return valve

85

Primary solar circuit pump

87

Safety valve calibrated at 6 bar

88

Solar expansion vessel

89

Heat transfer fluid container

112b

Domestic hot water sensor

114

Primary solar circuit filling and draining device

(a propylene glycol)

126

Solar regulator

130

Manual bleed degasser

131

Array of collectors

132

Solar station complete with DIEMASOL solar regulation

M001774-B

130

89

89

230V
50Hz

114

61

88

87

85

4

84

114

39

61

61

4. Installation

NEO 2.1 / SUN 211

69

20/02/2013 - 300024195-001-02