5 attaching the label, 5 checks and adjustments after commissioning, 6 changing the settings – DE DIETRICH ELITEC DTG 130 Eco.Nox User Manual
Page 27: Age: 27)

27
01/02/11 - 300002915-001-E
DTG 130 Eco.NOx
5.4.5
Attaching the label
Affix the label which indicates for which type of gas the boiler is fitted
and set.
5.4.6
Pressure setting and marking of calibrated injectors
(1)
15 °C - 1013 mbar
(a)
Availability in line with the country's sales plan.
5.5 Checks and adjustments after commissioning
Z
Carry out all the checks mentioned in the chapter "Checking
5.6 Changing the settings
Z
Control panel instructions
Models DTG ... Eco.NOx
133
(a)
134
135
136
137
138
(a)
139
(a)
Burner
nozzles
Natural gas H/E
GZ50
204B
204B
204B
204B
204B
210B
210B
Natural gas L/LL
GZ410
245B
245B
245B
245B
245B
245B
245B
Propane
140A
140A
140A
140A
140A
140A
140A
H - 13 mbar
225B
225B
225B
225B
225B
225B
225B
GZ350
310B
310B
310B
310B
310B
310B
310B
Manifold
pressure
Natural gas H/E
GZ50
mbar
16
16
16
16
16
15
15
Natural gas L/LL
mbar
12.1
12.1
12.1
12.1
12.1
12.1
12.1
GZ410
mbar
12.5
12.5
12.5
12.5
12.5
12.5
12.5
Propane
mbar
29
29
29
29
29
29
29
H - 13 mbar
mbar
10.2
10.2
10.2
10.2
10.2
9.6
8.4
GZ350
mbar
7
7
7
7
7
6.2
6
Gas flow
rate
Natural gas H/E
GZ50
m
3
/h
(1)
1.42
2.13
2.83
3.52
4.22
4.91
5.60
Natural gas L/LL
m
3
/h
(1)
1.65
2.47
3.29
4.10
4.91
5.71
6.51
GZ410
m
3
/h
(1)
1.71
2.56
3.41
4.25
5.09
5.92
6.75
Propane
Kg/h
1.04
1.56
2.07
2.59
3.10
3.60
4.11
H - 13 mbar
m
3
/h
(1)
1.42
2.13
2.83
3.52
4.22
4.79
5.13
GZ350
m
3
/h
(1)
1.97
2.95
3.92
4.89
5.87
6.50
7.29