beautypg.com

Legend – DE DIETRICH ELITEC DTG 130 Eco.Nox User Manual

Page 13

background image

13

01/02/11 - 300002915-001-E

DTG 130 Eco.NOx

„

Operating cycle with the downdraught thermostat
cut off

In the event of smoke release by the anti-blowback device, the anti-
release safety device switches off the burner with the safety box on
standby for 15 minutes (this is indicated by an alarm indicator
flashing). The 15 minute timed period can only be interrupted by a
sector cut.
To restart the boiler:
Wait for around 5 minutes (thermostat cooling time) and press the
reset button on the safety control box. If interruptions of this kind
happen repeatedly, contact your fitter.

„

Legend

A

Start of operation

A

1

Second ignition attempt

A

2

Third ignition attempt

B

Formation of flame in ignition burner

C

End of first ignition attempt

C

1

End of second ignition attempt

C

2

On safety through absence of flame signal

D

Anti-blowback thermostat cut

E

Resetting

F

Restart of the boiler

SF

Burner flame signal

TA

Ignition transformer

TAF

Anti-backflow thermostat

TCH

Boiler thermostat

VA

Safety lockout warning light

VBA

Ignition burner valve

VBP

Main burner valve

tn

Downdraught thermostat cooling time: times vary

ts

Safety time: 55 seconds

t

TAF

Waiting time: 15 minutes

Required input signals

Box output signals

Contact closed

8518N045

D

F

TCH

VA

TA

SF

VBP

TAF

VBA

t

TAF

t

n