64 table 9 - gas heater troubleshooting – AAON M2-036 User Manual

Page 64

background image

64

Table 9 - Gas Heater Troubleshooting


















LED

Code

System Description

Actions

None

No Power to

T1

On call for heat nothing happens

1. Check for open fuse or circuit breaker.
2. Check for poor wiring connection.
3. Check for failed 24V transformer.

Open Limit

Switch

Thermostat call for heat. No power

across terminals V1 / V2 control.

1. Check for proper operation of circulating air
supply system and for air filter blockage.
2. Check manifold pressure when limit cools and
closes. Natural gas 3.5” w.c / LP gas 10.0” w.c.
3. Low combustion blower air output. Flue gas
temp exceeds 550ºF. Inspect for debris
accumulation, proper wheel attachment, and
proper voltage to blower.

Steady

On

Internal

Control Fault

(No Operation)

24VAC across Terminal 24VAC /

V2-Gnd when Thermostat calling for

heat

Control fault – Replace ignition control.

1

Flash

Combustion

Air Flow Fault

Pressure switch contacts in closed

position for 30 seconds with no

output to Combustion blower.

Remains in this mode with

combustion blower off.

1. Check for short in wiring to pressure switch.
2. Check pressure switch for closed contacts (with
leads disconnected).
3. Replace pressure switch

Open pressure switch or flame

rollout switch when inducer (IND

terminal) is energized. If switch

remains open for more than 30

seconds after combustion blower is

energized, control will remain in this

mode with IND terminal (blower)

energized.

1. Failed Combustion blower.
2. Check connections and air tube from draft
inducer to air switch for leaks.
3. Check rollout switch manual reset - depress
reset.
4. Check supply tube from draft inducer housing
to pressure switches for condensate - drain line
and re-connect.
5. Check pressure switch for condensate
accumulation
6. Replace pressure switch