BEFORE START THE CHILLER, PLEASE READ THE FOLLOWING:

Start Up Check List

A supply water temperature sensor is being monitor to activate each refrigeration circuit
accordantly. For every temperature increase from the set-point, the controller determines the
stages to come on. A flow switch is equipped to ensure water flow exist in the system. This
flow safety switch prevents any refrigeration to activate if NO flow is detected. A pressure
regulator is installed on the discharge of the pump to regulator water pressure at various
conditions. The pressure regulator is set for 40pisg.

PLEASE VERIFY THE SETTING ON THE CONTROL MATCH THESE INFORAMTION:

Main page: Pressing PRG or ESC will return to Main page

Schreiber

Engineering
3-STAGES

CHILLER


Press ESC:

System

Status

Supply: ______F

Setpoint:

______F

Demand:______%

Press DN key:
Return:________F
Ambient:_______F

Press DN key:
Pump1:

ON/OFF

EN/DIS

Pump2:

ON/OFF

EN/DIS


It is advisable to enable both pumps as ONLY one pump is operated at a time.

Press DN key:

Comp1: ON/OFF

EN/DIS

Comp2: ON/OFF

EN/DIS

Comp3: ON/OFF

EN/DIS


Note: There is a square blinking at the upper left corner on the screen, pressing enter
key (arrow pointing to the left) will take the blinker to the pump. Using up or down arrow
key to toggle on/off. Continue pressing enter key will take you to next field. After all
settings are set, the blink MUST return to the upper left hand corner to store the data
and before going to the next screen.