Comp1: _______ PSI
Comp2: _______ PSI
Comp3: _______ PSI
PRESS PRG KEY gives:
MAIN
MENU
Temp
Setting
Comp
Setting
Pump
Setting
I/O
Setting
Temp
Setting:
Setpoint: _____
F
Set desire chiller water supply temperature
Band:________
F
Set
desire
band.
A value of 3 is recommended
Int:__________
sec Time between band degree in seconds
HiTemp
Set:
_____F Hi
temperature set-point
HiTemp
band:____
F Hi Temperature Band
HiTemp EN: en/dis
Hi Temperature control
Comp/Fan
Setting:
Min
On:_______
sec
Compressor
minimum ON time in seconds
Min
Off:_______
sec
Compressor
minimum OFF time in seconds
TBS:_________
sec
Time between stage to be ON in seconds
Fan 1/2/3 Setting:
Pres.
Set:_____psi
Head
Pressure set point (OFF=Values)
Band:________psi
Head
Pressure band (ON=Pres. Set + band)
Delay:_______sec
Time
delay
for
sensor
failure
Pump
Setting:
No
setting
required
I/O
setting:
Low
pressure
switch
Start
delay:_____
sec
Delay time on start in seconds
Run delay:_____
sec Delay time on run in seconds
High
pressure
switch
Start
delay:_____
sec
Delay time on start in seconds
Run delay:_____
sec Delay time on run in seconds
Flow
switch
Start
delay:_____
sec
Delay time on start in seconds
Run delay:_____
sec Delay time on run in seconds
These delays will generate the system alarm if condition is not satisfied after the
set time.