PLANNING DATA


Chiller Installation

The chiller and condenser should be installed on a level surface or sub base. Vibration isolation
is not provided by Schreiber Engineering and should be installed per requirements of local codes.
The bolt pattern diagram contains the corner weights for chiller and condenser mounted together
(AC configuration). (SEE DRAWING ON THE BACK FOR DETAIL ON CLEARANCE AND
WEIGHT INFORMATION)

The chiller should be installed in an area free from dirt and debris than can clog the condenser
coil. It should also not be installed near any places where hot exhaust air would enter the
condenser.

WEIGHT
CHILLER (DRY WEIGHT)

2500 lbs

HVAC Requirements:


If the condenser is installed indoors, adequate fresh air must be brought into the space and
exhausted. If the chiller section only is installed indoors, a small amount of heat is added to the
space and should be accounted for in HVAC load calculations.

HEAT REJECTION (BTU/HR) AIRFLOW (CFM)
CHILLER 2,500 N/A
CONDENSER CONDENSER WATER FLOW NEED: 45 GPM

Electrical Data


MODEL

FLA

MIN SUPPLY

MAX FUSE

15MED-WC-480/3

37 46 55

15MED-WC-230/3

72 89 95


Each chiller has one non-fused disconnect. The branch circuit for the chiller should be protected
by fuses no larger than listed in the above table. If more than one chiller is to be installed, each
chiller requires a dedicated, fused circuit.

REMOTE TERMINAL

The remote terminal can be installed in any indoor location. It is connected to the chiller via a 6-
conductor data cable. It is terminated with phone jack style connectors. The remote terminal is
wall mounted. Refer