Page 10
REMOTE CONDENSER PIPING (NOT APPLICALBE FOR WC)
There are two circuits in this chiller; therefore four pipes are required to connect the chiller and
condenser.
Refrigeration Piping Guidelines (Based on 150ft equivalent length)
Hot Gas Line (comp-to-condenser) 1-1/8”
Liquid Line (condenser-to-receiver) 7/8”
These values are based on 150’ of total piping length, plus equivalent length of fittings. Shorter
runs may allow for smaller pipes, but over-sizing the Hot Gas line lowers the gas velocity, which
prevents proper oil movement through the system. This value MUST NOT BE EXCEEDED, for
any length of pipe.
Refer to the interconnecting diagram for more requirements on piping installation.
See also other documents in the category Schreiber Chillers Equipment:
- Copy of 1000AC MRI (42 pages)
- 1000AC (30 pages)
- 1000ACsf (30 pages)
- 1001ACsf (26 pages)
- 1250ACsf (30 pages)
- 1055 Clearances (2 pages)
- 100ACsf (32 pages)
- 1001acsfod (31 pages)
- 15 Med Main Manual (19 pages)
- 1500ACsf (31 pages)
- 150AC laser (34 pages)
- 150ACsf (30 pages)
- 150ACsfaw (32 pages)
- 15MEDAC email (64 pages)
- 15MEDAC_GEN2 (77 pages)
- 2500modify (19 pages)
- 2500ACsf (31 pages)
- 200ACsf (31 pages)
- 2000ACsfmodify (20 pages)
- 2203AC - 3-Stage Chiller (40 pages)
- 2000ACsf (31 pages)
- 30AC (18 pages)
- 400ACsf trane (35 pages)
- 400ACsf (32 pages)
- 500ACsf (33 pages)
- 50ACsf (32 pages)
- 750AC MRI (43 pages)
- 750ACsf (31 pages)
- 400AC MRI (40 pages)
- 300ACsf (31 pages)
- 3000ACsf (32 pages)
- 3000AC (33 pages)
- 300AC-MRI (46 pages)
- Modular Chillers (56 pages)
- Micro Photonix 1001ac (35 pages)
- MICRO MAX CHILLERS (21 pages)
- MC75WC (13 pages)
- MC75AC (20 pages)
- Katema 1001AC (45 pages)
- Hypertherm Part No 039104 (30 pages)
- Excellon (26 pages)
- Excellon MM30AC (20 pages)
- Excellon 150EX (34 pages)
- Excellon 150AC (33 pages)