Atec Tenney-ETCU-16 User Manual
Page 2
Model
ETCU–09
ETCU–16
ETCU–30
ETCU–64
Interior Volume
9 cu. ft.
16 cu. ft.
30 cu. ft.
64 cu. ft.
256 liters
460 liters
850 liters
1,812 liters
Interior Dimensions
24 x 25 x 26
36 x 26 x 30
40 x 36 x 36
48 x 48 x 48
WxDxH - inches (mm)
(610 x 635 x 660)
(914 x 660 x 762)
(1016 x 914 x 914)
(1219 x 1219 x 1219)
Exterior Dimensions
34 x 73 x 78
46 x 74 x 82
50 x 87 x 88
58 x 99 x 100
WxDxH - inches (mm)
(864 x 1854 x 1983)
(1169 x 1881 x 2084)
(1271 x 2211 x 2237)
(1474 x 2516 x 2542)
Nominal Horsepower
3.5 x 3.5
6 x 6
10 x 10
3.5 x 3.5
6 x 6
10 x 10
3.5 x 3.5
6 x 6
10 x 10 15 x 15
3.5 x 3.5
6 x 6
10 x 10 15 x 15
Rated Horsepower
2.5 x 2.5
5 x 5
10 x 10
2.5 x 2.5
5 x 5
10 x 10
2.5 x 2.5
5 x 5
10 x 10 15 x 15
2.5 x 2.5
5 x 5
10 x 10 15 x 15
Compressor Type
Scroll
Scroll
Scroll
Scroll
Noise (dBa)
Heating
60
60
60
60
60
60
60
60
60
60
60
60
60
60
Cooling
68
75
75
68
75
75
68
75
75
75
68
75
75
75
Heating
Elements (Kw)
230/460
6
12
12
6
12
12
6
12
12
24
6
12
12
24
208V
4.5
9
9
4.5
9
9
4.5
9
9
18
4.5
9
9
18
Model
ETCU–09
ETCU–16
ETCU–30
ETCU–64
Cooling Rate (min)
190
°
C to -65
°
C
49
34
14
78
36
19
155
76
31
20
256
125
52
42
71
°
C to -65
°
C
36
26
11
40
28
15
119
59
26
17
197
97
44
33
85
°
C to -40
°
C
27
18
8
32
20
12
95
42
21
12
157
69
36
24
Heating Rate (min)
-65
°
C to 190
°
C
35
16
16
32
22
22
60
30
30
20
110
53
53
27
-65
°
C to 71
°
C
17
8
8
14
11
11
27
13
13
10
45
23
23
13
-40
°
C to 85
°
C
16
8
8
12
10
10
27
13
13
11
45
23
23
14
Water Cooled
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Air Cooled
Y
Y
Y
Y
Y
Y
Y
208/230V-1 Ph
Y
N/A
N/A
Y
N/A
N/A
Y
N/A
N/A
N/A
Y
N/A
N/A
N/A
208/230V-3 Ph
Y
Y
N/A
Y
Y
N/A
Y
Y
N/A
N/A
Y
Y
N/A
N/A
460V-3 Ph
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Y
Air Delivery
(Blower HP)
.5 HP
(2) .5 HP
(2) .75 HP
(2) .75 HP
Airfl ow (CFM)
750
1600
1600
1600
Temp Unif. (Std
Dev/9 Pt)
+/-0.5
°
C/+/-1
°
C
+/-0.5
°
C/+/-1
°
C
+/-0.5
°
C/+/-1
°
C
+/-0.5
°
C/+/-1
°
C
Temp Control
+/-0.3
°
C
+/-0.3
°
C
+/-0.3
°
C
+/-0.3
°
C
* Single Stage Refrigeration Temperature Range: -35°C to 200°C
* Performance is based upon an empty chamber operatfing at 24°C (75°F) ambient air and may vary slightly at other ambient temperatures. Voltages
below those listed may affect performance. All performance data is for 240 or 480V / 60Hz operation.
* Liquid Nitrogen is available as an option on all systems. When Liquid Nitrogen is provided, the heater KW is automatically upgraded to the maximum
for that chamber size. Consult factory for current draw of any Liquid Nitrogen equipped chambers.
* Airflow circulation is based on blower wheel performance curves. Actual circulation rate will vary depending on the cooling option selected.
* Temperature uniformity Standard deviation from the mean, measured at –25°C and 100°C. 9 Point: Uniformity measured in accordance with ASTM
E145 section 4 at temperatures of –25°C and 100°C.
* Test chamber performance may be affected by the addition of certain optional accessories.
* Chamber operation utilizing 50Hz power utility will derate performance approximately 17%
* It is Thermal Product Solutions' policy to constantly improve quality, features and performance. Thermal Product Solutions reserves the right to
change specifications without notice.
Gruenberg, Blue M, Tenney
Mailing Address: P.O. Box 150 | White Deer, PA 17887-0150 | USA |
Phone: (570) 538-7200 | Fax: (570) 538-7380
Physical Address: 2821 Old Route 15 | New Columbia, PA 17856-9396
[email protected]
Specifications & Product Information is subject to change without notice.
Images for reference only. Options and accessories may not be included with all models.