Ch 1

Ch 2

Ch 3

Ch 4

4Ø 4W / 4Ø 5W

1Ø 2W

1Ø 2W

1Ø 2W

1Ø 2W

3Ø 3W / 3Ø 4W / 4Ø 4W

1Ø 2W

3Ø 3W (Aron)

3Ø 3W (Aron)

3Ø 3W (Aron)

1Ø 2W

1Ø 2W

Device

Measured Value

Ch 1

Ch 2

Ch 3

Ch 4

Appropriate setting

of wiring

4Ø motors

Power of all windings

Phase 1

Phase 2

Phase 3

Phase 4

4+0

High power batterie

chargers (3Ø -> DC)

Input and output

power, efficiency

Phase 1

Phase 2

Phase 3

DC-Out

3+1

(UD I* -> U* I*)

Rectifier section of

inverters (3Ø -> DC)

Input power,

rectifier efficiency

Phase 1

Phase 2

Phase 3

DC-Bus

3+1

(UD I* -> U* I*)

Output section of

inverters (DC -> 3Ø)

Output power,

chopper efficiency

AC-Out 1 AC-Out 2 AC-Out 3

DC-Bus

3+1

(UD I* -> UD ID)

1Ø -> 3Ø inverter

Low power motor

drives

Input and output

power, efficiency

AC-Out 1 AC-Out 2 AC-Out 3

Phase 1

3+1

(UD I* -> U* I*)

Power supplies with

multiple outputs

Input and output

power, efficiency

DC-Out 1 DC-Out 2 DC-Out 3

Phase 1

3 +1

1Ø Transformers with

multiple output

windings

Input and output

power, efficiency

AC-Out 1 AC-Out 2 AC-Out 3

AC-In

3+1

3Ø laods with auxiliary

supplies

Complete input power

Phase 1

Phase 2

Phase 3

Aux. AC

or DC

3+1

(UD I* -> UD ID)

3Ø -> 3Ø inverter

High power motor

drives

Input and output

power, efficiency

AC-In 1

AC-In 2

AC-Out 1 AC-Out 2

2+2

(UD I* -> UD ID)

3Ø -> 1Ø

AC power source

Input-, output- and

DC-Bus power,

efficiency

AC-In 1

AC-In 2

DC-Bus

AC-Out

2+2

(UD I* -> U* I*)

4mm safety sockets

600V CAT III

Direct measurement

Standard current clamps

with current outputs >0.5A

Compensated

ZES current clamps

HD15 sockets

for external sensors

Magneto-resistive

current transducer modules

PSU200/400/600/700

Precision current transducer

Standard current clamps with

voltage/current (<0.5A)

outputs

Hall effect transducers

DC/AC current clamps with

voltage output

e.g. for oscilloscopes

0.6 ... 16A (6 Ranges)

DC ... 20 kHz

100A ... 3000A

45Hz ... 3kHz

1.2A ... 40A (6 Ranges)

5Hz ... 20kHz

5A ... 50A

DC ... 20KHz

1A ... 700A

peak

DC ... 20kHz

(300kHz, bandwidth of sensor

is limited by LMG450)

10A ... 200A

45Hz ... 3kHz

5A ... 200A

DC ... 20kHz

10A ... 200A

DC ... 20kHz

Compensated current clamp

Part No. L45-Z06

A special current measuring device is the
compensated current clamp by ZES ZIMMER.
It features electronic compensation of amplitude
and delay errors. Even at low current levels of
1A to 40A, measurement is exact in the frequency
range from 5Hz to 20kHz. Due to its high dynamic
common-mode rejection, this current clamp is also
very suitable for carrying out measurements at the
frequency inverter output.

Compensated current clamp L45-Z06

Various methods of applying current to be measured

4 independent power measuring channels

The current and voltage paths
of the four power measuring
channels are all isolated from
each other and from earth.
This allows a high degree of
measuring freedom in many
different power measurement
applications.
The adjacent table shows vari-
ous types of wirings for grouped
and individual measurement
channels. The table also assigns
application examples for the
respective types of wiring.
Power measurement channels
1 and 4 can each be synchro-
nised to their input signals
(fundamental waves etc.)
independent of each other.
Channels 1 and 4 are then the
synchronisation references for
the other channels contained in
groups A and B.
This is a very useful method for
carrying out efficiency measure-
ments for equipment where the
input and output have different
frequencies, for example a
3-phase frequency inverter with
single-phase mains supply.

Wiring settings in () are featured
by option „Star-Delta Conversion“

Group A

Group B