The control units are rated at 11.5kVA with a 2 second

overload capability of 23kVA using pulse mode. All metering

is digital and a memory facility is provided to hold the current

reading when the output trips or is switched off. The current

is thyristor controlled and is automatically switched off when

the device under test trips.

The PCU1 systems have a high accuracy timing system,

allowing timing tests to be carried out to a resolution of 1ms.

Selection for normally open or normally closed contacts is

automatic, and the status of the contacts is shown on the

front panel.

The PCU1 series are

medium powered primary current

injection systems offering output currents up to 5000A. The

system consists of a separate control unit containing all

metering and control functions and a loading unit that

provides the high current output. The PCU1-LT and PCU1-

SP are ideally suited to primary current injection, stability

testing and circuit breaker testing. In addition, the SP

version offers direct-reading CT ratio and polarity tests and

a 100A secondary injection output. T&R also offer the

higher-powered PCU1-HP and PCU2.

Features (PCU1-LT and PCU1-SP)

5kA maximum output current
(higher overload currents for 2s)

Multi-function digital timing system

Digital true RMS memory ammeter

Solid state switching

2000A and 5000A loading units

Three range outputs on loading units

Rugged, compact design

Optional trolley mounting of system

PCU1-SP Additional Features

Secondary injection up to 100A

Direct reading CT ratio and polarity

Timing modes are available to test under and over current

devices, re-closers, under and over voltage devices, current

trips and circuit breakers. A full range of high current output

leads are available to complement the system in a range of

lengths.

Two loading units are available, delivering a maximum output

current of 2000A or 5000A. Each loading unit has three

output taps to allow for a wide range of load impedances.

For example, the NLU5000 may be configured to either give

a maximum current of 5000A on the 2.3V range, 2500A on

the 4.6V range or 1250A on the 9.2V range.

PCU1-SP

PCU1-LT

Primary Current

Injection Systems

PCU1-SP & NLU5000 with

optional trolley

Feature

PCU1-LT

PCU1-SP

PCU2

Primary injection

ь

ь

ь

Max output power

11.5kVA

40s

11.5kVA

40s

20kVA

5 min

Secondary injection

ы

ь

ы

CT ratio/polarity test

ы

ь

ы

Output current Range Output state

1.000kA 5kA On
000.000s 5000.:5ACT

Timer Auxiliary metering