34

Example Applications

Busbar joint resistance

The DMO200 is ideal for measuring busbar joint resistance.
Before making connections ensure that the supply is off and
necessary earths have been applied. Connect the high current leads
to the busbar, ensuring that the joint resistance to be measured is
in the circuit. Connect the sense leads as close as possible to the
joint to be measured. Select the desired test current using one of
the preset test currents (or use the adjust knob to set a custom test
current). Switch the output on, and the current rises to the preset
current. Switch the output off again, and the reading is held on the
display.

Circuit breaker contact resistance

The DMO200 is suited to all low resistance measurements on power
systems, and is particularly suited to measuring contact resistances
on substation circuit breakers, isolators and grounding equipment.
The unit has a powerful output capable of driving 200A through 20m
output leads to reach the contacts of even the largest circuit
breakers. Optional output lead extensions are available which
extend the high current and sense leads by 3, 5 or 10m.

Accurate measurements on circuit breakers, isolators and grounding
links with both sides earthed are simple with the optional current
clamp. This allows the current flowing through the earthing
equipment to be subtracted from the test current.

B

u

s

b

a

r

B

u

s

b

a

r

Storing results

The DMO200 is supplied with a USB memory key and USB keyboard
for storing annotated results. To enter or edit a comment tap the
COMMENT/MENU button. The comment can then be edited using
the keyboard. This comment is stored with each result until a new
comment is entered. Each time the output of the unit is switched off
the readings from the unit are saved to the USB memory key in CSV
format along with the date, time and your comment.

The CSV file can be opened with any spreadsheet program such as
Microsoft Excel™ or OpenOffice Calc.

Details

Supply requirements:

90-265Vac 1300VA max

Output:

1-200Adc 5V

Resistance measurement:

0.1



-5

DMO200 dimensions:

360 x 290 x 165mm

DMO200 weight:

6.9kg

Accessories supplied with unit: Mains lead, user manual,
3m high current leads, 3m sense leads, spare fuses.

Optional accessories

DMO200 current clamp

Part no. A224-0001

3m Kelvin clamp lead set in plastic case

Part no. A224-0003

Output/sense extension 3m in plastic case

Part no. A224-0004

Output/sense extension 5m in plastic case

Part no. A224-0005

Output/sense extension 10m in plastic case Part no. A224-0006