FLUKE-753 Documenting Process Calibrator

FLUKE-754 Documenting Process Calibrator-HART

Standard accessories include: Three sets of stackable

test leads, three sets of TP220 test probes with three

sets of “extended tooth” alligator clips, two sets AC280

hook clips, BP7240 Li-ion battery pack, BC7240 battery

charger, C799 field soft case, USB communication cable,

getting started guide, instruction manual on CDROM,

NIST traceable certificate of calibration, DPC/TRACK 2

sample software that enables upload and printing of

calibration records. Model Fluke-754 includes HART

communication cable. Includes C799 Field Soft Case.

Includes three year warranty.
FLUKE-750SW DPC/TRACK 2 Software

Included with DPC/TRACK software:

Software media, Instruction Manual, USB Cable.
FLUKE-700 Pxx Pressure Modules

Included with each Fluke Pressure Module:

BP-ISO Adapter(s) (except with P29 - P31), Instruction

Sheet, NIST traceable calibration report and data,

one-year warranty.
Accessories

Fluke-700PMP

Pressure Pump; 100 psi/7 bar

Fluke-700LTP-1

Low Pressure Test Pump

Fluke-700PTP-1 Pneumatic Test Pump;

400 psi/40 bar

Fluke-700HTP-1 Hydraulic Test Pump;

10,000 psi/700 bar

Fluke-700HTH-1 Hydraulic Test Hose

Fluke-700PRV-1 Pressure Relief Valve Kit for HTP

Fluke-700-IV

Current Shunt (for mA/mA

applications)

Fluke-700PCK

Pressure Calibration Kit

Fluke-700TC1

TC Mini-Plug Kit, 9 types

Fluke-700TC2

TC Mini-Plug Kit, JKTERS

Fluke-700TLK

Process Test lead kit

754HCC

Smart instrument

communication cable

BC7240

Battery Charger

BP7240

Li-on Battery Pack

C700

Hard Carrying Case

C781

Soft Carrying Case

C799

Soft Field Case

Ordering information

Data log function

Measure functions: Voltage, current, resistance,

frequency, temperature, pressure

Reading rate: 1, 2, 5, 10, 20, 30, or 60 readings

per minute

Maximum record length: 8000 readings

(7980 for 30 or 60 readings per minute)
Ramp function

Source functions: Voltage, current, resistance,

frequency, temperature

Rate: 4 steps/second

Trip detect: Continuity* or voltage

*Continuity detection not available when sourcing current

Loop power function

Voltage: 26 V

Accuracy: 10 %, 18 V minimum at 22 mA

Maximum current: 25 mA, short-circuit protected

Maximum input voltage: 50 V dc

Note: 250 Ω series resistance is automatically supplied whenever loop power is

enabled on 754.

HART modem interface (754 only)

Maximum input voltage: 30 V dc

Environmental specifications

All calibrator specifications apply from +18 °C to

+28 °C unless stated otherwise.

Operating temperature: -10 °C to 50 °C

Storage temperature: -20 °C to 60 °C

Operating altitude: 3000 m above mean sea level

(9842 ft)

90-day specifications: The standard specification

intervals for the 750 Series are 1 and 2 years.

Typical 90-day measurement and source accuracy can

be estimated by dividing the one year “% of reading”

or “% of output” specifications by 2. Floor specifications,

expressed as “% of f.s.” or “counts” or “ohms” remain

constant.

Ingress protection: IP-52
Power: Internal battery pack li-ion, 7.2 V, 4400 mAh,

30 Wh; Battery life: Typical usage, >8 hours

Dimensions: 136mm x 245mm x 63 mm

(5.4 in x 9.6 in x 2.5 in)

Weight: 1.2 kg (2.7 lb)

Side port connections:

Pressure module connector

USB connector to interface to your PC

Digital instrument (HART) connector

Connection for optional battery charger/eliminator

Safety: Complies with CAN/CSA C22.2 No 1010.1-92,

ANSI/ISA S82.01-1994, UL3111, and EN610-1:1993.

Data storage capacity:

1 week of calibration procedures and results

11 Fluke Corporation 750 Series Brochure

Fluke Corporation

PO Box 9090,

Everett, WA 98206 U.S.A.

Fluke.

Keeping your world up and running.

®

Fluke Europe B.V.

PO Box 1186, 5602 BD

Eindhoven, The Netherlands

For more information call:

In the U.S.A. (800) 443-5853 or Fax (425) 446-5116

In Europe/M-East/Africa +31 (0) 40 2675 200 or Fax +31 (0) 40 2675 222

In Canada (800)-36-FLUKE or Fax (905) 890-6866

From other countries +1 (425) 446-5500 or Fax +1 (425) 446-5116

Web access: http://www.fluke.com

©2004-2011 Fluke Corporation. Specifications subject to change without notice.

Printed in U.S.A. 9/2011 1263323L B-EN-N

Modification of this document is not permitted without written permission from

Fluke Corporation.