Atec Megger-BM Series User Manual

Page 3

background image

BM11, BM11D, BM21 and BM25

5 kV Analogue/Digital Insulation Testers

BM21

BM25

All BM11D features plus:

All BM21 features plus:

n

Variable test duration controlled by timer

n

RS232 real time download

n

Variable test voltage in 25 V steps to 5000 V

n

Dielectric Discharge Test

n

Leakage current and capacitance measurement

n

Automatic Polarisation Index Tests

n

Breakdown or Burn modes

n

Automatic Step Voltage Tests

n

Tests to 5,000 G

BM21: as BM11D plus;

n

Variable test voltage in 25 V steps

n

Breakdown or ‘Burn’ modes allow choice of diagnostic

approach

n

Shows capacitance at end of test

n

Timer sets test duration for easier test control

n

Tests to 5,000 GΩ

n

Leakage current mode

BM25: as BM21 plus;

n

Automated testing for increased productivity

n

Polarisation Index and Step Voltage tests

n

Dielectric Discharge test for multilayer insulation

n

Optically isolated RS232 port for real-time download

Test voltages (d.c.) 500, 1000, 2500, 5000 V

500, 1000, 2500, 5000 V

Accuracy (20°C)

±5% on open circuit

±5% on 100 MΩ load

Insulation

100 kΩ to 100 GΩ; at all test voltages

Digital 10 kΩ to 50 GΩ @ 500 V

Resistance

10 kΩ to 100 GΩ @ 1000 V

Range

10 kΩ to 250 GΩ @ 2500 V

10 kΩ to 500 GΩ @ 5 kV

Analogue 100 kΩ to 1 TΩ @ all voltages

Basic Accuracy

±1,5% of arc length

±5% of reading 10 MΩ to 100 GΩ @ 5 kV

Short Circuit

Current

1 mA nominal, 2 mA max.

1,8 mA nominal, 2 mA max.

Voltage Range

50 to 1000 V d.c. or a.c.

50 to 1000 V d.c. or a.c.

Accuracy (20°C)

±5% ±10 V

±2% ±1 V

Display

Analogue

Analogue/digital (3 digits)

Interference

Rejection

2 mA a.c. (50/60 Hz) on 5 kV range

1 mA r.m.s. per kV to a maximum 2 mA

Capacitor

Discharge Time

<1 s per µF to discharge from 5000 V to 50 V

<2 s per µF to discharge from 5000 V to 50 V

Leakage current
measurement

None

None

Capacitance

measurement

None

None

Timer

None

Automatic; 0 to 60 minutes

Temperature

Operating -15 to +55°C (5 to +131°F)

Operating -20to +50°C (-4 to 122°F)

Range

Storage -40 to +65 °C (-40 to +149°F)

Storage -25 to +65 °C (-13 to +149°F)

Temperature

Coefficient

< 0,04% of arc length per °C (0.2%/°F)

(Applies over range 0 to 30°C) (32 to 86°F)

0,2% per °C (0.1%/°F) for test currents >100 nA 0,1% per °C to test voltage (0.05% per °F)


Humidity Range

90% RH @ 40°C max. (104°F)

90% RH @ 40°C max. (104°F)

Safety

IEC348

IEC1010-1 (1995), EN61010 (1995) to installation

category III, 300 V, phase to earth, 500 V phase to phase

Test voltages (d.c.)

500, 1000, 2500, 5000 V; plus 25 to 5000 V in 25 V steps

Accuracy (20°C)

±5% on 100 MΩ load ±25V for test voltages <500 V

Insulation

Digital

10 kΩ to 500 GΩ @ 500 V

Resistance

10 kΩ to 1 TΩ @ 1000 V

Range

10 kΩ to 2,5 TΩ @ 2500 V

10 kΩ to 5 TΩ @ 5 kV

Analogue 100 kΩ to 1TΩ @ all voltages

Basic Accuracy

±5% of reading 1 MΩ to 1 TΩ @ 5 kV (0 to 30°C) (32 to 86°F)

Short Circuit

Current

1.8 mA nominal, 2 mA max.

Voltage Range

50 to 1000 V d.c. or a.c. (0 to 5000 V d.c. when testing)

Accuracy (20°C)

±2% ±1 V

Display

Analogue/digital (3 digits)

Interference

Rejection

1 mA r.m.s. per kV to a maximum 2 mA

Capacitor

Discharge Time

<2 s per µF to discharge from 5000 V to 50 V

Leakage current
measurement

0,01 nA to 999 µA Accuracy ±5% ±0,2 nA

Capacitance

measurement

0,01 - 10,0 µF (displayed at end of test) Accuracy ±15% ±0,03 µF

Timer

User selectable 0 to 90 minutes. Test is terminated at end of preset time

Temperature

Operating -20 to +50 °C (-4 to 122 °F)

Range

Storage -25 to +65 °C (-13 to +149 °F)

Temperature

Coefficient

(Applies over range 0 to 30 °C) (32 to 86 °F)

0,2% per °C for test currents >100 nA

Humidity Range

90% RH @ 40°C max. (104°F)

Safety

IEC1010-1 (1995), EN61010 (1995) to installation

category III, 300 V, phase to earth, 500 V phase to phase