beautypg.com

Thumper specification review – Atec High-Voltage-CDS Series User Manual

Page 4

background image

4

CDS-3616U(F) & CDS-3632U(F) - The Network Systems Thumper

Input:

CDS-3616U/3632U:

120 V, 60 Hz, 25 A

CDS-3616UF/3632UF: 230 V, 50/60 Hz, 15 A

Hipot Output:

0 – 9/18/36 kVdc

Hipot Burn Current: 280/140/70 mAdc
Discharge Output:

CDS-3616U(F): 1600 Joules at each output voltage

CDS-3632U(F): 3200 Joules at each output voltage

Discharge Rate:

6 – 10 seconds

TDR Interface:

Arc Reflection & Current Impulse

Size:

25”w x 29”d x 44.5”h (30”w with attached cable reel)

635 mm w x 737 mm d x 1130 mm h

Weight:

1600J model: 375 lbs/170 kgs

3200J model: 450 lbs/204 kgs

Cable Outputs:

100’ HV, return, & ground

Cable Reels:

100’ HV & return cable reel

Optional

100’ ground cable reel

Thumper equipped with10’ output cable with

MC connection to reel

Other Features:

Rugged, transit protected meters

External Interlock

Emergency OFF mushroom switch

Plexiglas panel to view grounding solenoid

Internal heater to limit condensation

CDS-3616U(F) & CDS-3632U(F)

(suffix F for 230 V 50/60 Hz models)

These two models are ideal for Network Systems or other situations where cables are rated up to 69kV, oil insulated cables, and/or long
cable lengths are encounted. The powerful 3200 joule pulse makes fault locating easier using acoustical and electro-magnetic detection
devices. With 280 mA of burn current, faults can be rapidly reduced to low voltage levels, permitting thumping at lower and less damaging
voltage levels. The CDS-3632U can thump at 9kV, 18 kV, or 36 kV yet deliver 3200 joules.

There is no better thumper. The CDS-3616/32U offers the complete package: three full joule output voltages, three variable hipot

outputs, 280 mA burn current, variable discharge rate, tdr/radar ready, and its extremely durable design holds up to years of use.
Another plus: all HVI Thumpers use EPR high voltage output cable rather than XLPE. EPR stays flexible in cold weather. HVI thought
of everything.

Thumper Specification Review

Don’t handicap your fault finding efforts by buying a thumper with only half the features necessary.

For the same money, you can buy a full featured thumper. When specifying, require:

• At least two full joule output voltage settings, preferably three, and with at least 1000 joules of energy

• A variable hipot output with high burn current of at least 200mA

• Variable discharge rate from 6 – 10 seconds

• A remote TDR/radar, not one built-in, for flexibility, versatility, ease in service, and ease in use

Compare HVI Features and Specifications to Any Other – Why Utilities Choose HVI

Features

CDS-2010U

CDS-3616U

CDS-3632U

Output Voltages

0 – 5/10/20 kV

0 – 9/18/36 kV

0 – 9/18/36 kV

Joules

1000 @ 5/10/20 kV

1600 @ 9/18/36 kV

3200 @ 9/18/36 kV

Constant Energy

Yes. On all taps

Yes. On all taps

Yes. On all taps

Variable Hipot

Yes. On all taps

Yes. On all taps

Yes. On all taps

Hipot/Burn Rating

400 mA

280 mA

280 mA

Discharge Rate

6 – 10 seconds

6 – 10 seconds

6 – 10 seconds

TDR/Radar Ready

Yes

Yes

Yes

HVI Offers the Complete Package – Don’t Buy Less