TTR™100

Handheld TTR

Automatic self-calibration for each test.

Rugged, lightweight design ideally suited for a harsh

field and substation environment.

Three user selectable standards: ANSI, IEC, and

Australian. Also meets IEC61010-1, CE, and IP54

requirements for protection against ingress of dust

and water.

Six user selectable languages: English, French, German,

Italian, Portuguese and Spanish.

SPECIFICATIONS

Type of Power

Rechargeable NiMH battery pack, 3.6 V dc, 3800 mAh

Battery Life

15 hours of field operation

Charger input voltage

100-250 V ac, 50/60 Hz ±2 Hz Unit can be operated while

charging. Charging time is approximately three hours

Optional charger source

Optional inverter 12 V dc to 115 V ac for powering a charger from

vehicle battery (non CE marked)

Excitation Voltage

8 V rms for testing distribution or power transformers, and PTs;

1.5 V ac RMS, or 8 V ac RMS for testing CTs.

The excitation voltage is switched automatically if excitation

current exceeds a preset value.

Test Frequency

55 Hz internally generated providing a universal 50/60 Hz test set

Excitation Current Range

0 to 100 mA, 4-digit resolution

Turns Ratio Range

8 V ac: 0.8 to 20,000, 5 digit resolution (for transformers and PT

testing)

1.5 V ac: 5.0 to 2200, 5 digit resolution (for CT testing)

Phase Deviation Range

±90º, 1 decimal point for the minutes display, 2 decimal points for

the degree display, or for the centiradian display

Winding Resistance Range

0 to 2000

, 4 digit resolution

Transformer Vector Group

1PH0 or 1PH6

Transformer Polarity

Additive or Subtractive

Current (rms) accuracy

±(2% of reading + 1 digit)

Phase Deviation Accuracy

±3 minutes

Turns Ratio Accuracy

±0.1% (0.8 to 2000)

±0.15% (2001 to 4000)

±0.20% (4001 to 10,000)

±0.25% (10,001 to 20.000)

Winding Resistance Accuracy

±(10% of reading + 1 digit) for 10

to 2000

range

±(10% ±1 m

) for 10 m

to 9.99

range

±(10% ±0.5 m

) for 0.1 m

to 9.99 m

range

PC/Printer Interface

RS232C port, 9-pin, 57.6 Kbaud (19.2 Kbaud for the printer)

Display full graphics

LCD module, wide temperature range, 128 x 64 dots (21

characters by 8 lines)

Test Result Storage

Internal, nonvolatile memory for storing up to 200 sets of single-

phase measured and calculated ratio, exciting current, phase, ratio

error, winding resistance, polarity, vector group, plus header

information (company, substation, transformer manufacturer,

transformer rating, instrument serial number, temperature, relative

humidity, and operator name)

In addition, up to 100 user-defined transformer settings can be

stored.

Computer Software

Included software for downloading of data to a PC, data storage

to database and report printout.

Test Leads

Supplied with one complete set of single-phase leads, 6 ft (1.8 m)

in length

Transformer Winding Phase Relationship

ANSI C57.12.70-1978

CEI/IEC 76-1:1993 and Publication 616:1978

AS-2374, Part 4-1982 (Australian Standard)

Safety/EMC/Vibration

Meets the requirements of IEC-1010-1, CE and ASTM D999.75

Temperature Range

Operating: -4º F to 131º F (-20º C to 55º C)

Storage:

-58º F to 140º F (-50º C to 60º C)

Relative humidity

Operating: 0 to 90% noncondensing

Storage:

0 to 95% noncondensing

Protective Devices

High voltage side shorting relays, transient voltage suppressors

and gas surge voltage protectors

Measuring Time

8 to 20 seconds for a single-phase distribution transformer

Measurement Method

ANSI/IEEE C57.12.90

Dimensions

9.5 H x 4.5 W x 1.875 D in. (241 H x 115 W x 48 D mm)

Weight

Approx. 3.3 lbs (1.5 kg), instrument only, without leads

Protective Instrument Carrying Case

Neoprene case with carrying strap and attachable pouch for

universal charger and 6 ft. (1.8 m) test leads, single-phase

connection (two leads for the H winding and three leads for the

secondary winding with tap).