beautypg.com

Atec Megger-TTR100 User Manual

Page 2

background image

TTR™100

Handheld TTR

APPLICATIONS

The proper operation of a transformer relies almost

entirely on the electrical properties of its windings. To

ensure continued proper operation, transformers are tested

to verify that their electrical properties have not changed

from design specifications. A TTR is an extremely useful

instrument for testing transformer windings because it can

locate several types of problems within a single- or a

three-phase transformer. It is also ideal to use for testing in

meter shops for the inspection of CTs and PTs. It can

determine the no-load accuracy of CTs and PTs and also

determine the need to further test faulty CTs and PTs.

The TTR100 applies voltage, with voltage ratio being

directly proportional to turns ratio, to the high-voltage

winding of a transformer and accurately measures the

resulting voltage from the low voltage winding. In addition

to turns ratio, the unit measures excitation current, phase

angle deviation between the high and low voltage

windings, percent ratio error, dc winding resistance and

polarity.

Transformer Turns Ratio

Transformer Turns Ratio is the ratio of the number of turns

in the high voltage winding to that in the low voltage

winding.

A Transformer Turns Ratio Test Set such as the TTR100 can

directly measure the ratio of single phase, as well as three

phase transformers. Transformer ratio can change due to

several factors, including physical damage from faults,

deteriorated insulation, contamination and shipping

damage. If a transformer ratio deviates more than 0.5

percent from the rated voltage ratio, it may not operate

reliably. To measure small ratio changes such as this, the

accuracy of a Megger TTR100 is needed.

Excitation Current

The TTR100 is capable of measuring exciting current by

applying voltage to one of the transformers windings. An

accurate measurement of exciting current can provide

information about the condition of a transformer’s core.

Unwanted circulating currents or unintentional grounds

can affect the exciting current and indicate a problem.

Phase Angle Deviation

The phase angle deviation is the relationship between the

voltage signal applied to the high voltage winding and the

voltage signal extracted from the low voltage winding.

The phase deviation between the high and low side of a

transformer is generally very small. However, the phase

deviation can change significantly if there is deterioration

or damage in the transformer core. The TTR100 can

measure this phase relationship with the resolution

necessary to detect a problem.

Additional information about a transformer’s electrical

properties can be found in the IEEE Standard Test Code

for Transformers, C57.12.90, or by contacting Megger’s

technical support group.

Winding Resistance

Measuring the DC resistance of transformer windings will

aid in identifying problems such as shorted or open

windings, as well as loose connections.

The Megger TTR100 can measure the DC resistance of

both single phase and three phase transformer windings.

Transformer Polarity

Polarity of a distribution transformer becomes of interest in

order to determine its proper connection within a power

network.

The Megger TTR100 will identify subtractive and additive

polarity of the single-phase distribution transformers.

FEATURES AND BENEFITS

Faster, easier handheld operation. User no longer has to

kneel or bend down to operate the instrument.

Powered by rechargeable battery, provides up to fifteen

hours of field operation.

Report header information such as company name,

substation name, transformer manufacturer, transformer

ratio, operator, temperature and %RH can be entered

and saved via the alphanumeric keypad.

Measures the widest turns ratio range in the industry

(20,000:1) with the highest accuracy (±0.1%, 0.8 to 2000)

at a low excitation voltage.

Enables the operator to enter the ratio of the transformer

and all of its taps. This allows the operator to know

immediately when a tap is outside the acceptable limits

so that problem taps can be easily identified.

Records ratio errors for bushing CTs to an accuracy of

±0.1% nameplate. This reduces the need for additional

test equipment and improves set-up time.

Measures the phase deviation (in minutes, degrees or

centiradians) of the transformer primary versus

secondary. This quickly indicates problems in the

transformer such as partial shorted turns and core faults.

This measurement is also useful in verifying phase errors

in all types of PTs and CTs.

Perfect for meter shops, the TTR100 can be used for

inspection purposes by using it to determine the no-load

accuracy of most CTs and PTs. It also can be used to

determine the need to further test potentially faulty CTs

and PTs.

The TTR100 is ideal for use by transformer

manufacturers. Its unique testing procedures and storage

capability allows an operator to set up and test single

and three-phase transformers (with multiple tap

changers and bushing CTs) in minimal time.

A “Quick Test” mode provides a fast determination of

the turns ratio, excitation current, phase angle deviation,

and winding resistance in single- and three-phase

transformers and CTs. In addition, polarity is provided

for CTs and single-phase transformers.

Displays all measured and calculated values for each test

including ratio, excitation current, ratio error, phase

angle deviation, transformer vector group, winding

resistance and polarity thus providing comprehensive

and conclusive data