beautypg.com

Specifications, Ordering information, Dlro 600 digital microhmmeter – Atec Megger-dlro-600 User Manual

Page 2

background image

automatically and may be recalled to the display or downloaded
for review.

SPECIFICATIONS

Measurement:
Range:

0.1 µ

to 999.9 m

(Subject to supply voltage and leads used)

Accuracy:

Voltage

±0.5% ± 0.1 mV

Current

±0.5% ± 0.1 A

Resistance:

Better than 1% from
100 µ

to 100 m

Output Current:
The chart above shows the maximum output current available at
different supply voltages with a 4 m

load (i.e. standard 5 m

current leads only) and with a 7 m

load

Current Lead Resistance (Megger supplied leads)
2 x 5 m 50 mm

2

current leads

4 m

2 x 10 m 70 mm

2

current leads

5.4 m

2 x 15 m 95 mm

2

current leads

6 m

Maximum Continuous Test Time
More than 60 seconds at 600 A @ 20ºC ambient.

ORDERING INFORMATION

Item (Qty)

Order No.

Megger DLRO600 High Current Digital Low Resistance

Ohmmeter (English QWERTY keyboard)

DLRO600 E

Megger DLRO600 High Current Digital Low Resistance

Ohmmeter (French AZERTY keyboard)

DLRO600 F

Complete with

5m Lead set in bag comprising:

6220-755

2 x 50mm

2 current leads with clamps and

2 x potential leads with clips.

Download Manager

6111-442

User Guide on CD-ROM

6172-763

RS232 download cable

25955-025

Quick Start Guide (English)

6172-782

Item (Qty)

Order No.

Quick Start Guide (French)

6172-783

Warranty card.

6170-618

Optional Accessories at extra cost

15m Lead set comprising 2 x 95mm

2 current leads with clamps and

2 x potential leads with clips.

6220-757

10m Lead set comprising 2 x 95mm

2 current leads with clamps and

2 x potential leads with clips.

6220-756

DLRO 600

Digital Microhmmeter

Power Supply for: See chart.

full output:

207 to 265 V 50/60 Hz with a load
less than 7 m

including current

leads

reduced output: Down to 100 V 50/60 Hz.
Test Modes:

Manual, Auto, Continuous.

Test Time:

7 seconds NORMAL /AUTO mode.
Refreshed every 2 seconds in CONTINUOUS
mode

Display:

Large, high resolution backlit liquid crystal
display

Warnings

Current flowing: - LED. Other warnings are
shown on the lcd display.

Data Transfer

Real time or batch download via RS232
using Download Manager.

Storage Capacity:

300 result sets and memo, battery backed for
10 years.

Memo field:

200 characters max.

Test Current
Range:

10 A to 600 A unsmoothed d.c. in 1 A steps

Accuracy:

±2% ±2 A

Voltmeter input
impedance:

>200 k

Hum rejection:

5 V rms 50 Hz/60 Hz

Temperature
Operation:

-10 to +50ºC

Storage:

-25 to +65ºC

Calibration:

20

o

C

Co-efficient:

<0.05% per ºC

Max. Humidity:

95% RH non-condensing

Maxi Altitude:

2000 m

Safety:

IEC61010 – (1995) Category II, 300 V phase
to earth.

EMC:

EN61326 annex A (heavy industrial)

Dimensions:

410 x 250 x 270 mm

Weight:

14.5 kg (excluding test leads)

700

600

500

400

300

200

100

0

100 120 140 160 180 200 220 240

Test Cur

rent (A)

Supply Voltage

4 m

Load

7 m

Load

UK

Archcliffe Road Dover
CT17 9EN England
T +44 (0) 1304 502101
F +44 (0) 1304 207342

UNITED STATES

4271 Bronze Way
Dallas TX 75237-1088 USA
T 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399

OTHER TECHNICAL SALES OFFICES

Norristown USA, Toronto CANADA,
Mumbai INDIA, Trappes FRANCE,
Sydney AUSTRALIA, Madrid SPAIN
and the Kingdom of BAHRAIN.

Registered to ISO 9001:2000 Reg no. Q 09290

Registered to ISO 14001 Reg no. EMS 61597

DLRO600_DS_en_V10

www.megger.com
Megger is a registered trademark