Atec Fluke-DTX Series User Manual
Page 3
** Note: all specifications for tests on twisted-pair cabling apply to 100
Ω cable. Contact Fluke Networks for information on measurement
performance for cable with a different impedance.
†
Length specs do not include the uncertainty of the cable’s NVP Value
Above specifications are subject to change without notice.
Environmental Specifications
Operating temperature
32° F to 104° F (0° C to 45° C)
Storage temperature
-4° F to +140° F (-20° C to +60° C)
Operating relative humidity
32° F to 95° F (0° C to 35° C): 0 % to 90 %
(% RH without condensation)
95° F to 113° F (35° C to 45° C): 0 % to 70 %
Vibration
Random, 2 g, 5 Hz -500 Hz
Shock
1 m drop test with and without module and adapter attached
Safety
CSA C22.2 No. 1010.1: 1992
EN 61010-1 1st Edition + Amendments 1, 2
Pollution degree
Pollution Degree 2 as defined in IEC 60664 and applied to IEC 60950 ‘Safety of Information
Technology Equipment, 1999’
Altitude
Operating: 4000 m; Storage: 12000 m
EMC
EN 61326-1
Performance Specifications**
Baseline accuracy
The baseline accuracy of all DTX Series testers meets or exceeds the requirements of Level IV as in
draft 2nd Edition of IEC 61935-1 over the frequency range supported by the tester.
Category 6/Class E link test modes
DTX CableAnalyzer far exceeds Level III requirements of TIA/EIA-568-B.2-2 and IEC 61935-1.
(and lower link categories)
Class F link test modes
DTX-1800 is compliant with Level IV requirements as in the draft 2nd edition of IEC 61935-1.
Length for Twisted Pair Cabling
†
Parameter
Single-ended Test
Dual-ended Test (Main and Remote)
Range
800 m (2600 ft)
150 m (490 ft)
Resolution
0.1 m or 1 ft
0.1 m or 1 ft
Accuracy
± (.3 m + 2%); for lengths 0 to 150 m
± (.3 m + 2%)
± (.3 m + 4%); for lengths 151 to 800 m
Propagation Delay
Parameter
Single-ended Test
Dual-ended Test (Main and Remote)
Range
4000 ns
750 ns
Resolution
1 ns
1 ns
Accuracy
± (2 ns + 2%); 0 to 750 ns
± (2 ns + 2%)
± (2 ns + 4%); 751 to 4000 ns
Delay Skew
Parameter
Twisted Pair Cabling
Range
0 ns to 100 ns
Resolution
1 ns
Accuracy
± 10 ns
DC Loop Resistance Test
Parameter
Twisted Pair Cabling
Range
O
Ω to 53 Ω
Resolution
0.1
Ω
Accuracy
± (1
Ω + 1%)
Overload recovery time
Less than 10 minutes to rated accuracy following over-voltage. Referencing is required after
repeated or prolonged over-voltage.
Fluke Corporation
P.O. Box 777, Everett, WA USA 98206-0777
Fluke Networks operates in more than 50 countries
worldwide. To find your local office contact details,
go to
www.flukenetworks.com/contact
.
©2004 Fluke Corporation. All rights reserved.
Printed in U.S.A. 6/2004 2131195 B-ENG-N Rev B
N E T W O R K
S U P E R
V I S I O N