SPECIFICATION - 800 L / 28
Cu
.
FT
. MODELS (460V)
7
Temp/Humidity
EGNX28-4CWL
EGNX28-4CAL
EGNX28-6CWL
EGNX28-6CAL
EGNX28-12CWL
EGNX28-15CW
Temp Only
EGNZ28-4CWL
EGNZ28-4CAL
EGNZ28-6CWL
EGNZ28-6CAL
EGNZ28-12CWL
EGNZ28-15CW
Temperature Range
-70 to 180°C (-94 to 354°F)
Cooling Capacity
2.5 kW at -50°C
3.6 kW at -50°C
5 kW at -50°C
9.4 kW at -50°C
Refrigeration System
Cascade 4 hp Scroll
Cascade 6 hp Scroll
Cascade 12 hp Scroll
Cascade 15 hp Discus
Heating System
10 kW
10 kW
15 kW
20 kW
Humidity Range
10 to 95% RH per chart (EGNX models only)
Measured Airflow
1,350 cubic meters per hour (800 CFM)
Performance Example (-40°C to 85°C with 50 lbs. Aluminum)
Heating Rate
10°C/m average
10°C/m average
13.5°C/m average
20°C/m average
Cooling Rate
3.1°C/m average
5.5°C/m average
13.5°C/m average
20°C/m average
Dimensions
Workspace Volume
800 L (28 cu. ft.)
Workspace (WxDxH)
1000 x 800 x 1000 mm (39.4" x 31.5" x 39.4")
Exterior (WxDxH)
1290 x 2159 x 1920 mm (51" x 85" x 76")
(CAL suffix models are 36 cm (14") taller)
1290 x 3074 x 2014 mm
(51" x 121" x 79.5")
Site Requirements
Power Supply
460V 3Ø 60Hz (380-415V 3Ø 50Hz also available)
Humidity Water
De-ionized water, 0.2 to 10 µS/cm resistivity (EGNX models only)
Cooling Water Maximum
with 30°C Inlet
34 LPM (9 GPM)
(CWL suffix models)
53 LPM (14 GPM)
(CWL suffix models)
102 LPM (27 GPM)
121 LPM (32 GPM)
Heat to Room
40,000 BTU/hr
(CAL suffix models)
60,000 BTU/hr
(CAL suffix models)
—
—
Temp/Humidity
EGNL28-4CWL
EGNL28-4CAL
EGNL28-6CWL
EGNL28-6CAL
EGNL28-7.5CWL
EGNL28-12CWL
Temperature Range
-40 to 180°C (-40 to 354°F)
Cooling Capacity
3.3 kW at -20°C
4.3 kW at -20°C
5.2 kW at -20°C
10.5 kW at -20°C
Refrigeration System
Single-stage 4 hp Scroll
Single-stage 6 hp Scroll
Single-stage 7.5 hp Scroll
Single-stage 12 hp Scroll
Heating System
10 kW
10 kW
15 kW
15 kW
Humidity Range
10 to 95% RH per chart
Measured Airflow
1,350 cubic meters per hour (800 CFM)
Performance Example (0°C to 80°C with 50 lbs. Aluminum)
Heating Rate
10°C/m average
10°C/m average
15°C/m average
20°C/m average
Cooling Rate
5°C/m average
10°C/m average
15°C/m average
20°C/m average
Dimensions
Workspace Volume
800 L (28 cu. ft.)
Workspace (WxDxH)
1000 x 800 x 1000 mm (39.4" x 31.5" x 39.4")
Exterior (WxDxH)
1290 x 2159 x 1920 mm (51" x 85" x 76")
(CAL suffix models are 36 cm (14") taller)
Site Requirements
Power Supply
460V 3Ø 60Hz (380-415V 3Ø 50Hz also available)
Humidity Water
De-ionized water, 0.2 to 10 µS/cm resistivity
Cooling Water Maximum
with 30°C Inlet
35 LPM (9 GPM)
(CWL suffix models)
55 LPM (14 GPM)
(CWL suffix models)
79 LPM (19 GPM)
106 LPM (27 GPM)
Heat to Room
52,000 BTU/hr
(CAL suffix models)
75,000 BTU/hr
(CAL suffix models)
—
—
RANGE -40 TO 180°C
RANGE -70 TO 180°C