beautypg.com

Atec EM-Test-EFT-500N5 Series User Manual

Page 2

background image

DATA SHEET > EFT 500N5-series > 20130321

TECHNICAL DETAILS

EFT 500N5 MODELS

EFT 500N5.1

With 3-phase coupler, 3x 440V/32A

EFT 500N5.2

With 3-phase coupler, 3x 440V/50A

EFT 500N5.5

With 1-phase coupler, 250V/32A

EFT 500N5.8

With 3-phase coupler, 3x 690V/32A

Other couplers on request

TEST LEVEL

Voltage range

200V - 4,800V

Into 50ohm

100V - 2,400V

Pulse shape

Into 50ohm load

Rise time tr

5ns ± 30%

Pulse width td

50ns ± 30%

Pulse shape

Into 1,000ohm load

Rise time tr

5ns ± 30%

Pulse width td

35ns to 150ns

Source impedance

50 Ohm ± 20%

Polarity

Positive/negative

TRIGGER

Release of Burst

Automatic, manual, external

Burst duration

Td = 0.1ms - 999.9ms

Burst repetition
rate

Tr = 10ms - 9,999ms

Spike frequency

f = 0.1kHz - 1,000kHz

Test duration

T = 0:01 min - 99:59 min
T > 99:59 min - endless

OUTPUT

Direct

Via HV coax connector

Coupler

L, N and PE, all combinations

DUT supply AC

single phase: 250V/32A, 50/60Hz
three-phase: 3x440V/32A or 50A,
50/60Hz

DUT supply DC

250V/10A

DUT supply

Other DUT supply voltages on
request

CRO Trigger

15V trigger signal for oscilloscope;
burst duration and pulse frequency
can be checked

TEST ROUTINES

Quick Start

Immediate start; easy to use and fast

User Test routines

Custom made test routine
Change voltage after T
Change frequency after T
Frequency sweep within a burst
Change burst duration after T
Random release of bursts
Synchronous burst mode
Change polarity after T

Standard Test
routines

As per IEC 61000-4-4,
Automatic test Level X - Y

Service

Service, set-up, self test

INTERFACES

Serial interface

USB

Parallel interface

IEEE 488, address 1 - 30

CN interface

To control external CNI 503

GENERAL DATA

Dimensions,
weight

EFT 500N5.1: 19"/6HU, 22kg
EFT 500N5.2: 19"/6HU, 40kg
EFT 500N5.5: 19"/3HU, 20kg
EFT 500N5.8: 19"/3HU, 23kg

Supply voltage

115/230V, +10/-15%

Fuses

2 x T 2AT (230V); 2 x T 4AT (115V)

OPTIONS

HFK

Coupling Clamp as per IEC
61000-4-4

KW 50

50ohm matching resistor for
verification

KW 1000

1,000ohm matching resistor for
verification

CA EFT kit

Kit for burst pulse verification
consisting of KW50, KW1000 and
adapter for DUT port with plastic
case for storage

A6dB

6dB attenuator

CNI 503

Coupling/decoupling networks,
3x440V/32-63-100A

iec.control

Software to control the test,
including standard library, test
report facility and data conversion
generator

www.emtest.com

© EM TEST > PAGE 2/3