Environmental, Dimensions, Maximum interference conditions at line – Atec Doble-M4100 User Manual

Page 2: Standards

background image

TOGETHER WE POWER THE WORLD

Doble Engineering Company
85 Walnut Street
Watertown, MA 02472 USA
tel +1 617 926 4900
fax +1 617 926 0528

MKT-SL-M4100TS-12/08

Doble is certified ISO 9001:2000

Temperature Measurement:

Range:

-20 °c to +50 °c

Resolution:

0.1 °c

Accuracy:

±4 °c

Requires optional temperature probe

ENVIRONMENTAL

Temperature

:

Operating:

-20 °c to +50 °c

Storage:

-

40 °c to +70 °c

Humidity:

90% non-condensing

DIMENSIONS

Instrument:

10-1/4 in. H x 20 in. W x

25-1/4 in. D

26 cm H x

50.8 cm W x 64.1 cm D

High Voltage Cable:

60 ft./18 mt (other lengths
available as options)

Weights

Instrument:

95 lbs/45.5 kg

MAXIMUM INTERFERENCE
CONDITIONS AT LINE

Frequency

Electrostatic:

15 ma rms of interference
current into any lead or
cable with no loss of
measurement accuracy.
applicable to a maximum
ratio of interference
current to specimen
current of 20:1.

Electromagnetic:

500 μT, at 50 Hz in any
direction

For more information, contact
[email protected]

The M4100 unit is the foundation of the M4000 Diagnostic
Test System for Condition Assessment of Power Apparatus

STANDARDS

EMC Emissions

FCC 47 CFR Part 15 Class A Emissions requirements (USA)
EN 55011:1998/A1:1999/A2:2002 Group 1 Class A ISM Emissions requirements (EUROPE)
AS/NZS CISPR 11:2004 Class A ISM Emissions requirements (Australia)

EMC Immunity

EN 61326:1997/A1:1998/A2:2001/A3:2003
IEC 61000-4-2/3/4/5/6/11
IEC 801-2(1984) Electrostatic Discharge
ANSI/IEEE C37.90.1 Surge Withstand Capability

SAFETY

EN 61010-1 :2001 (2nd Edition)

ENVIROMENTAL

IEC 60068-2-2 Dry Heat
IEC 60068-2-1 Cold
IEC 60068-2-30 Damp Heat

MECHANICAL

IEC 60068-2-27 Shock
IEC 60068-2-6 Vibration
IEC 60068-2-6 Drop test

ASTM D999.75 Transport Shock Test

Specifications are subject to change without notice.