M4100
Technical Specifications
The M4100 unit is the foundation of the M4000 Diagnostic Test System for Condition
Assessment of Power Apparatus
Note: A personal computer is required to operate the M4100
Power Specifications:
Output Voltage:
0 to 12 kV ac
Output Current:
100 ma continuous at 10 kV
200 ma > 30 minutes at 10 kV
300 ma > 4 minutes at 10 kV
Operating time period based on 50°c oper-
ating temperature. Longer durations at high
currents will be realized at lower operating
temperatures
Output Power:
3 kVa
Sinusoidal output signal internal generated
independent of input supply, No loss in per-
formance when used with portable generator
A.C. Input*:
95-264 V ac 47 to 63 Hz
16 a max at 110 V,
10 a max at 220 V
Measurement, Accuracy and
Range Test Frequency:
Test Frequency:
Range:
45 to 70 Hz independent
of input signa
l
Resolution:
0.1 Hz
Accuracy:
±1% of reading
Test Voltage:
Range:
25 V to 12 kV
Resolution:
1 V
Accuracy:
±1% of reading, ±1 V
Test Current:
Range:
0 to 5.0 a
Resolution:
0.1 μa
Accuracy:
±1% of reading, ±1 μa
Capacitance
:
Range:
0 to 100 μF
Resolution:
0.01 rF
Accuracy:
± 0.5% of reading, ± 1 rF
Inductance:
Range:
6 H to 10 MH
Resolution:
0.01 H
Accuracy:
± 0.5% of reading
Watts:
Range:
0 to 2 kW, actual
Resolution:
0.5 mW
Accuracy:
± 2% of reading at 10 kV,
± 0.03% of Va, ±0.5 mW
Dissipation Factor:
Range:
%PF
0 to ±100.00%
PF
0 to ±1.0000
% Tan d
0 to ±999.99%
Tan d
0 to ±9.9999
mW/Var
0 to ±9999.9
Resolution:
0.01% / 0.0001
Accuracy:
± 0.5% of reading
,
typical
±0.04% PF/Tan d
±0.0004 PF/Tan d
* There are power restrictions for input
voltages below 190 V AC.