beautypg.com

Specifications, Dielectric – Atec AEMC-CA6121 User Manual

Page 4

background image

C.A 6121

(Great Britain model)

................P01.1456.02

C.A 6121

(Continental Europe model)

........P01.1456.01

Instruments supplied with :
1 mains lead, 3-core,
1 set of 2 keys to lock the instrument,
2 high voltage guns (2 m cable),
1 discharge cable,
2 continuity leads 2.5 m, with double
contact crocodile clips,
2 safety leads 3 m (red/ black),
2 crocodile clips (red/ black),
1 test prod (red), 1 carrying bag
for the accessories and the user manual

Additional accessories :

PC software
« C.A 6121 TRANSFER » ....P01.1019.15
supplied with cable RS232 DB9M/DB25F
+ adapter DB25M/ DB9F

Serial printer ....................P01.1029.01
supplied with cable RS232 DB9M/ DB9M

Remote control pedal ......P01.1019.16

Signalling lights ................P01.1019.17

2 high voltage guns
(fitted with cable 6 m) ........P01.1019.18

Specifications

DIELECTRIC

Nominal test voltage (50 Hz)*

1000 V

1250 V

1500 V

Triggering current

1, 3, 5, 10, 20, 30, 40, 50, 60, 70,

80, 90, 100, 150, 200, 250, 300,

350, 400, 450, 500 mA

1, 3, 5, 10, 20, 30, 40, 50, 60,

70, 80, 90, 100, 150, 200, 250,

300, 350, 400 mA

1, 3, 5, 10, 20, 30, 40,

50, 60, 70, 80, 90, 100, 150,

200, 250, 300, 333 mA

* Test voltage greater than 1000, 1250 or 1500 V / 50 Hz at a voltage U

mains

= 230 V and a power P

load

= 500 VA

Display

Test voltage

Test current (sinusoidal)

Range

0...2.00 kV

0...199.9 mA

200...500 mA

Resolution

10 V

0.1 mA

1 mA

Accuracy

±(2% L + 20 V)

±(2% L + 0.3 mA) *

* ± (2% rdg + 0.5 mA) if triggering current set to 30, 40, 50, 60, 70, 80, 90 or 100 mA and ± (2% rdg + 2 mA) on 150, 200, 250, 300, 330, 350, 400, 450 or 500 mA

Display of the character of the test current : resistive, capacitive or absolute value

Timer : without or adjustable from 1 s to 5 min

INSULATION RESISTANCE

CONTINUITY

DISCHARGE TIME

GENERAL SPECIFICATIONS

Display

Insulation resistance

Test voltage

Range *

0...1.999 M

2.00...19.99 M

20.0...199.9 M

200...500 M

0...1200 V

Resolution

1 k

10 k

100 k

1 M

1 V

Accuracy

±(2% L + 2 pt)

±10% L

±(2% L + 2 pt)

* automatic ranges

Display

Voltage drop (

U)

Resistance (R

10A

) *

Test voltage

Test current

Range

0...10 V

0...999 m

1.00...1.99

0...12 V

0...9.99 A

10.0...25.0 A

Resolution

0.01 V

1 m

10 m

0.01 V

0.01 A

0.1 A

Accuracy

±(2% L + 0.02 V)

±(2% L + 2 m

)

± 5% L

±(2% L + 0.02 V)

±(5% L + 2 pt)

±3% L

* automatic ranges

Rated voltage : 500 or 1000 V ...

Measurement current : 1 mA min

Measurement with or without adjustable threshold value (0.2...500 M

)

Timer : without or adjustable from 2 s to 10 min

Display

Discharge time

Range

0...10 s

Resolution

0.1 s

Accuracy

±(2% L + 0.2 s)

Level of safety voltage : 60 V

Automatic threshold of discharge time :

1 s at the power supply terminals (2 point measurement)
5 s at the internal components (4 point measurement)

Max service voltage: 600 V AC/DC

Mains voltage : 230 V / 50 Hz

Max power absorbed : 600 VA

LCD screen : dot matrix 128 x 64 with
permanent backlighting and adjustable contrast

Interface : RS232

Memories : 999 values

Remote control signals : On / Off and Record

Working temperature : 0...50°C

Working humidity : 85% RH max (0...+40°C)

Dimensions (W x D x H) : 400 x 260 x 250 mm

Weight : 11 kg

Protection index : IP 40 (open) IP 54 (closed)

Protection of measurement circuits : by HBC

fuses

Electrical safety : IEC 1010-1 Cat III 600 V

Applicable standards :

EN 60204-1 “ Test of electric machines ”
VDE 104 “ Installation and operation of electric
test equipment ”
EN 61180-1 and -2 “ High voltage test techniques
for low voltage equipment ”

To Order

Voltage drops (

U) max pre-set, depending on the cross section of the cable :

Cross-section of the cable tested

0,5 mm

2

0,75 mm

2

1 mm

2

1,5 mm

2

2,5 mm

2

4 mm

2

6 mm

2

Max voltage drop

5 V

5 V

3.3 V

2.6 V

1.9 V

1.4 V

1.0 V

Measurement of low resistance (R

10A

) with or without adjustable

threshold value (10...2000 m

)

Max output voltage : 12 V~

Timer : without or adjustable from 1 to 15 s

Measurement

current (0...0.5

) : > 10 A ~

Connection system : 4-wire

FRANCE
190, rue Championnet
75876 PARIS Cedex 18
Tél. : (33) 01 44 85 44 85
Télex 269816 - Fax : (33) 01 46 27 73 89

7

S U B S I D I A R I E S

W O R L D - W I D E

906 111 632 - Ed.1 - 11/97 Non contr

actual document - Confir

m specifications bef

ore order

ing - Photos Blaise PAST

OR

-

- 01 41 41 08 94

UNITED KINGDOM
Waldeck House - Waldeck Road
Maidenhead SL6 8BR
Tel. : 1628 788 888
Fax : 1628 628 099